77 Ill. Adm. Code 350.2740
Electrical Systems
Section 350
Section 350.2740Â Electrical
Systems
a)Â Â Â Â Â Â Â Â General Electrical System Requirements
1)Â Â Â Â Â Â Â Â All material including equipment, conductors, controls, and
signaling devices shall be installed to provide a complete electrical system
with the necessary characteristics and capacity to supply the electrical
facilities required by these standards. All materials shall be listed as
complying with the applicable standards of Underwriters' Laboratories, Inc. or
other similarly established standards.
2)Â Â Â Â Â Â Â Â All electrical installations and systems shall be tested to
show that the equipment is installed and operates as planned or specified and
be in accordance with these this Subpart.
3)Â Â Â Â Â Â Â Â The installation shall meet all the requirements of NFPA 70.
b)Â Â Â Â Â Â Â Â Switchboards and Power Panels. Circuit breakers or fusible
switches that provide disconnecting means and overcurrent protection for
conductors connected to switchboards and panelboards shall be enclosed or
guarded to provide a dead-front type of assembly. The main switchboard shall
be located in a separate enclosure accessible only to authorized persons. The switchboard
shall be convenient for use, readily accessible for maintenance, clear of
traffic lanes, and located in a dry ventilated space free of corrosive fumes or
gases. Overload protective devices shall be suitable for operating properly in
ambient temperature conditions.
c)Â Â Â Â Â Â Â Â Panelboards. Panelboards that serve lighting and appliance
circuits shall be located on the same floor as the circuits they serve. This
requirement does not apply to emergency system circuits.
d)Â Â Â Â Â Â Â Â Lighting
1)Â Â Â Â Â Â Â Â All spaces occupied by people, machinery, and equipment within
buildings, approaches to and exits from buildings, and parking lots shall have
lighting.
2)        Resident's rooms shall have general lighting. A vandal-proof
reading light shall be provided for each resident. At least one light fixture
shall be switched at the entrance to each resident room. All switches for
control of lighting in residents' sleeping areas shall be of the quiet
operating type.
e)Â Â Â Â Â Â Â Â Receptacles (Convenience Outlets)
1)Â Â Â Â Â Â Â Â Each resident room shall have at least three duplex grounding
type receptacles:Â One located on each side of the head of each bed; one for
television if used; and one on another wall. Receptacles shall be located
between 12 to 30 inches above the finished floor.
2)Â Â Â Â Â Â Â Â Resident bathrooms shall have at least one duplex receptacle.
3)Â Â Â Â Â Â Â Â See Article 517 of NFPA 70 for grounding requirements.
4)Â Â Â Â Â Â Â Â Duplex receptacles shall be installed approximately 50 feet
apart in all corridors and within 25 feet from the ends of corridors.
f)Â Â Â Â Â Â Â Â Door Alarm System. Each exterior door shall be equipped with a
signal that will alert staff if a resident leaves the building. Any exterior
door that is supervised during certain periods may have a disconnect device for
part-time use. If there is constant supervision of the door 24 hours a day, a
signal is not required.
g)Â Â Â Â Â Â Â Â Fire Alarm System
1)Â Â Â Â Â Â Â Â A manually and automatically operated fire alarm system shall
be installed.
2)Â Â Â Â Â Â Â Â Automatic smoke detectors shall be installed in all resident
rooms and at 30 feet on center in all corridors other than sleeping area
corridors.
h)Â Â Â Â Â Â Â Â Emergency Electrical System
1)Â Â Â Â Â Â Â Â To provide electricity during an interruption of the normal
electric supply, an emergency source of electricity shall be provided and
connected to certain circuits for lighting and power. The emergency system
shall comply with NFPA 70, NFPA 99, AND NFPA 100, as applicable.
2)Â Â Â Â Â Â Â Â The source of this emergency electrical service shall be a
Level I or Level II, Class X, Type 10 emergency generating set approved by the
Department.
3)Â Â Â Â Â Â Â Â Details
A)Â Â Â Â Â Â Â The life safety branch and critical branch shall be in
operation within ten seconds after the interruption of normal electric power
supply.
B)Â Â Â Â Â Â Â Receptacles connected to emergency power shall be distinctively
marked.
C)Â Â Â Â Â Â Â The emergency generator shall not be solely dependent upon a
public utility gas system for the fuel supply. The facility shall maintain a
written procedure for automatically transferring from one fuel supply to
another when dual fuel supplies are used.
D)Â Â Â Â Â Â Â When fuel storage facilities are provided on the site, the fuel
tank shall have minimum capacity for 24-hour operation of the generator.