77 Ill. Adm. Code 350.3970
Electrical Systems
Section 350
Section 350.3970Â Electrical
Systems
a)        Resident's rooms shall have general lighting. At least one
light fixture shall be switched at the entrance to each resident room.
b)Â Â Â Â Â Â Â Â Duplex Receptacles in Resident Bedrooms
1)Â Â Â Â Â Â Â Â There shall be one duplex receptacle for each 12 lineal feet
of wall space in bedrooms. Doors are not included in measuring wall space.Â
Receptacles shall be located at convenient places.
2)Â Â Â Â Â Â Â Â For facilities which are licensed on or before October 1,
1987, and for which the Department has waived compliance with subsection (b)(1)
of this Section prior to that date, compliance with that subsection is not
required as long as the facility continues to comply with the conditions of the
waiver.
c)Â Â Â Â Â Â Â Â At least one duplex receptacle shall be installed in all
corridors which are ten feet or longer in length.
d)Â Â Â Â Â Â Â Â Panelboards serving lighting and appliance circuits are not
required to be located on the same floor as the circuits they serve.