77 Ill. Adm. Code 350.3980
Fire Alarm and Detection System
Section 350
Section 350.3980Â Fire Alarm
and Detection System
a)Â Â Â Â Â Â Â Â An approved automatic smoke detection system shall be
installed on each floor level. Such system shall be installed in accordance
with NFPA 101, Section 6-3 of the 1976 edition of the Life Safety Code, and
with NFPA Standard 72, 1975 edition. The smoke detectors shall be installed in
all rooms and corridors except toilets and closets. In no case shall smoke
detectors be spaced further apart than 30 feet on center, or more than 15 feet
from any wall. The automatic smoke detection system shall be electrically
interconnected to the fire alarm system. Facilities of eight beds or less will
be required to have this automatic smoke detection system. However, this
automatic smoke detection system will not have to be electrically connected to
the fire alarm system in accordance with this Section, if the facility has been
inspected by the Office of the State Fire Marshal and found not to need such
electrical connection to the fire alarm system, as evidenced by a written
report to the Department from the Office of the State Fire Marshal to that
effect. (A, B)
b)Â Â Â Â Â Â Â Â The fire alarm system shall automatically transmit the alarm
to any available municipal fire department by direct private line or through
any approved central station. Facilities of eight beds or less will not be
required to have this automatic fire alarm system in accordance with this
Section, if the facility has been inspected by the Office of the State Fire
Marshal and found not to need such fire alarm system, as evidenced by a written
report to the Department from the Office of the State Fire Marshal to that
effect. (A, B)