77 Ill. Adm. Code 370.2800
Electrical Systems
Section 370
Section 370.2800Â Electrical
Systems
a)Â Â Â Â Â Â Â Â All material including equipment, conductors, controls, and
signaling devices shall be installed to provide a complete electrical system
with the necessary characteristics and capacity to supply the electrical
facilities required by these Standards. All materials shall be listed as
complying with available standards of Underwriters' Laboratories, Inc. or other
similarly established standards.
b)Â Â Â Â Â Â Â Â All spaces occupied by people, machinery, and equipment within
buildings, approaches to and exits from buildings, and parking lots shall have
lighting.
c)        Residents' rooms shall have general lighting. At least one
light fixture shall be switched at the entrance to each resident room. All
switches for control of lighting in residents' sleeping areas shall be of the
quiet operating type.
d)Â Â Â Â Â Â Â Â Receptacles (Convenience Outlets)
1)Â Â Â Â Â Â Â Â Each resident bed room shall have duplex grounding type
receptacles as follows:Â At least one located at the head of each bed; one for
television if used; and one on another wall. Receptacles are to be located
between twelve (12) to thirty (30) inches above the finished floor.
2)Â Â Â Â Â Â Â Â Resident bathrooms shall have at least one duplex receptacle.
3)Â Â Â Â Â Â Â Â At least one duplex receptacle shall be installed in each
corridor.