77 Ill. Adm. Code 370.2810
Fire Alarm and Detection System
Section 370
Section 370.2810Â Fire Alarm
and Detection System
a)Â Â Â Â Â Â Â Â Provide an approved supervised fire alarm system.
b)Â Â Â Â Â Â Â Â An approved automatic smoke detection system shall be
installed on each floor level. Such system shall be installed in accordance
with National Fire Protection Association Standard 101, Section 6-3 of the l976
Life Safety Code, and with National Fire Protection Association Standard 72,
l975. In no case shall smoke detectors be spaced further apart than thirty (30)
feet on center, or more than fifteen (15) feet from any wall.
c)Â Â Â Â Â Â Â Â The automatic smoke detection system shall be electrically
interconnected to the fire alarm system.
d)Â Â Â Â Â Â Â Â The fire alarm system shall automatically transmit the alarm
to any available municipal fire department by direct private line, or through
any approved central station.