77 Ill. Adm. Code 390.2720
Mechanical Systems
Section 390
Section 390.2720Â Mechanical
Systems
a)Â Â Â Â Â Â Â Â General Mechanical System Requirements
1)Â Â Â Â Â Â Â Â Mechanical systems shall be tested, balanced, and operated to
demonstrate that the installation and performance of these systems conform to
the requirements of this Section.
2)Â Â Â Â Â Â Â Â Upon the completion of the contract, the owner shall be
furnished with a complete set of manufacturer's operating and preventative
maintenance instructions, a parts list with numbers and descriptions for each
piece of equipment, and a copy of the air-balance report. A complete set of
these documents shall be kept on the premises.
3)Â Â Â Â Â Â Â Â The owner shall be provided with instructions in the
operational use of the systems and equipment.
b)Â Â Â Â Â Â Â Â Thermal and Acoustical Insulation shall be provided as set
forth in the ASHRAE Handbook of Fundamentals and the Handbook of Applications
and NFPA 90A. Commercial kitchen grease hoods shall be insulated according to
NFPA 96 and in accordance with the insulation manufacturer's installation
instructions. Domestic water piping that is accessible to residents shall be
insulated as required by the Illinois Accessibility Code. Insulation shall be
provided for the following:
1)Â Â Â Â Â Â Â Â Boilers, smoke breeching, and stacks;
2)Â Â Â Â Â Â Â Â Steam supply and condensate return piping;
3)Â Â Â Â Â Â Â Â Hot water piping above 180 degrees Fahrenheit and all water
heaters, generators, and convertors;
4)Â Â Â Â Â Â Â Â Hot water piping above 125 degrees Fahrenheit that is exposed
to contact by residents;
5)Â Â Â Â Â Â Â Â Chilled water, refrigerant, and other process piping and
equipment operating with fluid temperatures below the ambient dew point;
6)Â Â Â Â Â Â Â Â Water supply and drainage piping on which condensate may occur;
7)Â Â Â Â Â Â Â Â Air ducts and casings with outside surface temperatures below the
ambient dew point; and
8)Â Â Â Â Â Â Â Â Other piping, ducts, and equipment as necessary to maintain
the efficiency of the system.
c)Â Â Â Â Â Â Â Â Insulation may be omitted from hot water and steam condensate
piping that is not subject to contact by residents when the insulation is not
necessary for preventing excessive system heat loss or excessive heat gain.
d)Â Â Â Â Â Â Â Insulation, including finishes and adhesives on exterior
surfaces of ducts, pipes, and equipment, shall have a flame spread rating of 25
or less and a smoke developed rating of 50 or less as determined by an
independent testing laboratory in accordance with the American Society for Testing
and Materials Standard E84. Exception: Duct, pipe and equipment coverings shall
not be required to meet these requirements if they are located entirely outside
of a building, or do not penetrate a wall or roof, or do not create an exposure
hazard.
e)Â Â Â Â Â Â Â Â Steam and Hot Water Systems. Supply and return mains and
risers for cooling, heating, and process steam systems shall be valved to
isolate the various sections of each system. Each piece of equipment shall be
valved at the supply and return ends.
f)Â Â Â Â Â Â Â Â Thermal Hazards. Any surface that is accessible to residents
and exceeds a temperature of 140 degrees Fahrenheit (such as radiators, hot
water or steam pipes, baseboard heaters, or therapy equipment) shall be
provided with partitions, screens, shields, or other means to protect residents
from injury. Any protective device shall be designed and installed so that it
does not present a fire or safety hazard or adversely affect the safe operation
of the equipment.
g)Â Â Â Â Â Â Â Â Heating, Ventilating, and Air Conditioning Systems
1)
Areas of a facility used by residents of the facility
shall
be air conditioned and heated by means of operable air-conditioning and
heating equipment. The areas subject to this air-conditioning and heating
requirement include, without limitation, bedrooms or common areas such as
sitting rooms, activity rooms, living rooms, community rooms, and dining rooms.
(Section 3-202(8) of the Act)
A)Â Â Â Â Â Â Â The mechanical system shall be capable of maintaining a
temperature of at least 75 degrees Fahrenheit.
B)Â Â Â Â Â Â Â The air-conditioning system shall be capable of maintaining an
ambient air temperature of between 75 degrees Fahrenheit and 80 degrees
Fahrenheit.
2)Â Â Â Â Â Â Â Â All ventilation supply, return, and exhaust systems shall be
mechanically operated.
3)Â Â Â Â Â Â Â Â Outdoor air intakes shall be located as far as practical, but
not less than 15 feet, from the exhaust outlets of ventilation systems,
combustion equipment stacks, plumbing vent stacks, or areas that may collect
vehicular exhaust and other noxious fumes, including the exhaust stream from
fuel-fired heating, ventilating and air conditioning (HVAC) sections. The
bottom of outdoor air intakes serving central systems shall be located as high
as practical, but not less than six feet above ground level, or, if installed
above the roof, three feet above roof level. Â For fuel-fired heating sections
of rooftop HVAC units, the exhaust vent may discharge not less than 36 inches
above the highest point of the fresh air intake hood in lieu of the 15-foot
separation.
4)Â Â Â Â Â Â Â Â The ventilation systems shall be designed and balanced to
provide the pressure relationships and ventilation rates as required under
ANSI/ASHRAE/ASHE Standard 170-2008, Ventilation of Health Care Facilities.
5)Â Â Â Â Â Â Â Â A differential pressure measuring device shall be installed
across each filter bed serving a central air system. The device may be a
remote readout instrument if the remote readout is readily visible in a
location accessible to the maintenance staff, or if the readout is displayed on
an interactive screen.
6)Â Â Â Â Â Â Â Â Air conditioning and ventilating systems shall be designed,
installed, and maintained as required by NFPA 90A. Â For areas within the
footprint of the facility that are heated by fuel-fired appliances using an
air-to-air heat exchanger, no fewer than two carbon monoxide (CO) detectors
shall be installed in the area served by each heat exchanger. One CO detector
shall be installed within five feet of a supply duct and one within five feet
of a return or exhaust duct. CO detectors shall be line or system powered and
shall signal the building fire alarm system when activated. If detectors are
line powered, a battery back-up or connection to the emergency power system is
required.
7)Â Â Â Â Â Â Â Â The hood and duct system for cooking equipment used in
processes that produce smoke or grease-laden vapors shall comply with NFPA 96. The
hood's extinguishment system shall be connected to the building fire alarm
system and shall initiate a general alarm when activated. Duct insulation that
is used in lieu of spacing from combustible construction members shall terminate
at the top of the hood on the lower end, covering the duct collar, and shall
pass through any combustible nailer opening in the roof/ceiling assembly and
into the roof jack assembly. The material used shall be installed exactly as
the manufacturer's installations require.
8)Â Â Â Â Â Â Â Â The ventilation of the medical gas storage and manifold rooms
shall comply with the requirements of NFPA 99, Standard for Health Care
Facilities, as applicable, including the gravity option system. Â If a
concentrator is used simultaneously to fill a portable container and as a
patient breathing device, the standards in NFPA 99 governing the use of medical
gasses shall be observed.
9)Â Â Â Â Â Â Â Â Boiler rooms and other rooms having combustion equipment shall
be provided with sufficient outdoor air to maintain combustion rates of
equipment and limit temperatures to 20 degrees Fahrenheit over ambient air in
adjacent interior spaces. If sealed combustion units are in use, the discharge
line shall remain clear of any adjacent walk paths and not less than 15 feet
from any operable fenestration or air intake. NFPA 54 shall apply, including
the calculations for combustion air openings. Effective temperature shall be as
defined by ASHRAE Handbook of Fundamentals.
10)Â Â Â Â Â Â Â Rooms containing heat-producing equipment, such as boiler
rooms, heater rooms, food preparation centers, laundries, and sterilizer rooms,
shall be insulated and ventilated to prevent any floor surface above from
exceeding a temperature of 10 degrees Fahrenheit above the ambient room temperature.
11)Â Â Â Â Â Â Â Access for filter changing shall be provided within equipment
rooms.