77 Ill. Adm. Code 390.2730
Plumbing Systems
Section 390
Section 390.2730Â Plumbing
Systems
a)Â Â Â Â Â Â Â Â All plumbing systems shall be designed and installed in
accordance with the requirements of the Department's rules entitled
"Illinois Plumbing Code" (77 Ill. Adm. Code 890), except that the
number of resident required water closets, lavatories, bathtubs, showers, and
other fixtures shall be as required by the standards and the facility program. (B)
b)Â Â Â Â Â Â Â Â Plumbing Fixtures
1)Â Â Â Â Â Â Â Â Plumbing fixtures shall be of non-absorptive acid-resistant
materials.
2)Â Â Â Â Â Â Â Â The water supply spout for lavatories and sinks required for
filling pitchers for nursing staff and food handlers' handwashing, shall be
mounted so that its discharge point is a minimum distance of five inches above
the rim of the fixture. (B)
3)Â Â Â Â Â Â Â Â Handwashing lavatories used by nursing staff and food
handlers, shall be trimmed with valves which can be operated without the use of
hands. When blade handles are used for this purpose, the blade handles shall
not exceed four and one half inches in length, except the handles on clinical
sinks shall not be less than six inches in length.
4)Â Â Â Â Â Â Â Â Clinical rim flush sinks shall have an integral trap in which
the upper portion of the trap seal provides a visible water surface.
5)Â Â Â Â Â Â Â Â The potwashing sink shall be a three compartment sink with one
compartment at least 14 inches deep.
6)Â Â Â Â Â Â Â Â Shower bases and tub bottoms shall be designed with nonslip
surfaces. (B)
c)Â Â Â Â Â Â Â Â Water Supply Systems
1)Â Â Â Â Â Â Â Â Water supply systems shall be designed to supply water at
sufficient pressure and volume to operate all fixtures and equipment during
maximum demand periods.
2)Â Â Â Â Â Â Â Â Each water service main, branch main, riser and branch to a
group of fixtures shall be valved. Stop valves shall be provided at each
fixture.
3)Â Â Â Â Â Â Â Â Flush valves installed on plumbing fixtures shall be of a
quiet operating type, equipped with silencers.
4)Â Â Â Â Â Â Â Â Hot water distribution systems shall be arranged to provide
hot water of at least 100 degrees Fahrenheit at each hot water outlet at all
times.
5)Â Â Â Â Â Â Â Â Hot water available to residents at shower, bathing and
handwashing facilities shall not exceed 110 degrees Fahrenheit. (A, B)
6)Â Â Â Â Â Â Â Â Each hot water system serving resident areas shall include at
least one of the following equipment requirements to insure that the water
temperature does not exceed 110 degrees Fahrenheit:
A)Â Â Â Â Â Â Â A thermostatically controlled mixing valve, or
B)Â Â Â Â Â Â Â An aquastat which limits the water temperature in the water
heater to a maximum temperature of 110 degrees Fahrenheit and a solenoid
operated shut off valve activated by a sensing element in the water line which
shuts off the water and activates an alarm at the nurses station when the water
temperature exceeds 110 degrees Fahrenheit. (A, B)
d)Â Â Â Â Â Â Â Â Hot Water Heaters and Tanks
1)Â Â Â Â Â Â Â Â The hot water heating equipment shall have sufficient capacity
to supply water at the temperature and quantities in the following areas:
Resident
Service
Dietary
Laundry
gallons/hour/bed
6½
4
4½
Temperature
(Degrees Fahrenheit)
110
140*
180
*180 degrees Fahrenheit
water is required at dishwasher and pot and pan sink. Water temperatures to be
taken at the point of use or discharge of the hot water or inlet to processing
equipment.
2)Â Â Â Â Â Â Â Â Water storage tanks shall be fabricated of corrosion resistant
metal or lined with noncorrosive material.
e)Â Â Â Â Â Â Â Â Drainage Systems
Insofar as
possible drainage piping shall not be installed above the ceiling nor installed
in an exposed location in food preparation centers, food serving facilities,
food storage areas, and other critical areas. Special precautions shall be
taken to protect these areas from possible leakage or condensation from necessary
overhead piping systems. (B)
f)Â Â Â Â Â Â Â Â Nonflammable Gas System. Nonflammable medical gas systems if
installed shall be in accordance with the requirements of National Fire
Protection Association Standards 56A and 56F. (B)
g)Â Â Â Â Â Â Â Â Clinical Vacuum (Suction) Systems. Clinical vacuum systems if
installed shall be in accordance with the requirements of the Compressed Gas
Association Pamphlet P-2.l. (B)
h)Â Â Â Â Â Â Â Â Fire Extinguishing Systems
1)Â Â Â Â Â Â Â Â A complete automatic sprinkler system shall be installed
throughout all facilities regardless of construction type. (A, B)
2)Â Â Â Â Â Â Â Â All sprinkler and other fire extinguishing systems shall be designed
and installed in accordance with National Fire Protection Association Standard
101 and referenced codes. (A, B)
3)Â Â Â Â Â Â Â Â All sprinkler systems shall be maintained in accordance with
National Fire Protection Association Standard 13A. (A, B)