77 Ill. Adm. Code 390.3020
Mechanical Systems
Section 390
Section 390.3020Â Mechanical
Systems
a)Â Â Â Â Â Â Â Â Mechanical systems shall be maintained to assure proper
working order and safe operation. Instructions in the operational use of the
systems and equipment shall be available at the facility.
b)Â Â Â Â Â Â Â Â Thermal and Acoustical Insulation. Insulation shall be provided
for the following:
1)Â Â Â Â Â Â Â Â Boilers, smoke breeching, and stacks;
2)Â Â Â Â Â Â Â Â Steam supply and condensate return piping;
3)Â Â Â Â Â Â Â Â Hot water piping above 180 degrees Fahrenheit and all water
heaters, generators, and converters;
4)Â Â Â Â Â Â Â Â Hot water piping above 125 degrees Fahrenheit that is exposed
to contact by residents;
5)Â Â Â Â Â Â Â Â Chilled water, refrigerant, and other process piping and
equipment operating with fluid temperatures below the ambient dew point.
6)Â Â Â Â Â Â Â Â Water supply and drainage piping on which condensation may
occur;
7)Â Â Â Â Â Â Â Â Air ducts and casings with outside surface temperature below the
ambient dew point; and
8)Â Â Â Â Â Â Â Â Other piping, ducts, and equipment as necessary to maintain
the efficiency of the system.
c)Â Â Â Â Â Â Â Â Insulation may be omitted from hot water and steam condensate
piping that is not subject to contact by residents when the insulation is not
necessary for preventing excessive system heat loss or excessive heat gain.
d)Â Â Â Â Â Â Â Insulation on cold surfaces shall include an exterior vapor
barrier.
e)Â Â Â Â Â Â Â Â Insulation, including finishes and adhesives on exterior
surfaces of ducts, pipes, and equipment, shall have a flame spread rating of 25
or less and a smoke developed rating of 50 or less as determined by an independent
testing laboratory in accordance with ASTM Standard E 84. Exception: Duct, pipe,
and equipment coverings shall not be required to meet these requirements if they
are located entirely outside of a building, or do not penetrate a wall or roof,
or do not create an exposure hazard.
f)Â Â Â Â Â Â Â Â Supply and return mains and risers for cooling, heating and process
steam systems shall be valved to isolate the various sections of each system. Each
piece of equipment shall be valved at the supply and return ends.
g)Â Â Â Â Â Â Â Â Thermal Hazards. Any surface that is accessible to residents
and exceeds a temperature of 140 degrees Fahrenheit (such as radiators, hot
water or steam pipes, baseboard heaters, or therapy equipment) shall be
provided with partitions, screens, shields, or other means to protect residents
from injury. Any protective device shall be designed and installed so that it
does not present a fire or safety hazard or adversely affect the safe operation
of the equipment.
h)        Heating, Ventilating, Air Conditioning Systems
1)
Areas of a nursing home used by residents of the nursing
home
shall
be air conditioned and heated by means of operable
air-conditioning and heating equipment. The areas subject to this
air-conditioning and heating requirement include, without limitation, bedrooms
or common areas such as sitting rooms, activity rooms, living rooms, community
rooms, and dining rooms.
(Section 3-202(8) of the Act)
A)Â Â Â Â Â Â Â The mechanical system shall be capable of maintaining a
temperature of at least 75 degrees Fahrenheit, pursuant to the requirements of
Section 390.690(j).
B)Â Â Â Â Â Â Â The air-conditioning system shall be capable of maintaining an
ambient air temperature of between 75 degrees Fahrenheit and 80 degrees
Fahrenheit, pursuant to the requirements of Section 390.670(j).
2)Â Â Â Â Â Â Â Â Heaters or furnaces of a type to be installed under, in, or on
the floor are not permitted.)
3)Â Â Â Â Â Â Â Â All ventilation supply, return, and exhaust systems shall be
mechanically operated.
4)Â Â Â Â Â Â Â Â The kitchen shall be provided with ventilation for reasonable
comfort and with sufficient make-up air for the rangehood exhaust.
5)Â Â Â Â Â Â Â Â The laundry shall be provided with ventilation for reasonable
comfort, with air flowing from clean areas to soiled areas and with exhaust to
the outdoors
6)Â Â Â Â Â Â Â Â Outdoor intakes shall be located as far as practical, but not
less than 15 feet, from the exhaust outlets of ventilation systems, combustion
equipment stacks, plumbing vent stacks, or areas that may collect vehicular
exhaust and other noxious fumes. The bottom of outdoor air intakes serving
central systems shall be located as high as practical, but not less than six
feet above ground level, or, if installed above the roof, three feet above roof
level.
7)Â Â Â Â Â Â Â Â Air conditioning and ventilating systems shall be maintained
to comply with the requirements of NFPA 90A.
8)Â Â Â Â Â Â Â Â The hood and duct system for cooking equipment used in
processes that produce smoke or grease-laden vapors, such as griddle frying or
deep frying, shall comply NFPA 96. The hood's extinguishment system shall be
connected to the building fire alarm system and shall initiate a general alarm
when activated. Duct insulation that is used in lieu of spacing from
combustible construction members shall terminate at the top of the hood on the
lower end, covering the duct collar, and shall pass through any combustible
nailer opening in the roof/ceiling assembly and into the roof jack assembly.Â
The material used shall be installed exactly as the manufacturer's instructions
require.
9)Â Â Â Â Â Â Â Â Boiler rooms and other rooms housing combustion equipment
shall be provided with sufficient outdoor air to maintain proper combustion
rates of equipment and to limit room temperatures to 20 degrees Fahrenheit over
ambient inside air in adjacent interior spaces. If sealed combustion units are
in use, the discharge line is to remain clear of any adjacent walk paths and shall
be not less than 15 feet from any operable fenestration or air intakes. NFPA
54 shall apply, including the calculations for combustion air openings.
10)Â Â Â Â Â Â Â Â For areas within the footprint of the facility that are
heated by fuel-fired appliances using an air-to-air heat exchanger, not fewer
than two carbon monoxide (CO) detectors shall be installed in the area served
by each heat exchanger. One CO detector shall be installed within five feet of
a supply duct and one within five feet of a return or exhaust duct. CO
detectors shall be line or system powered and shall signal the building fire
alarm system when activated. If detectors are line powered, a battery back-up
or connection to the emergency power system is required.