77 Ill. Adm. Code 518.2190
Finishes
Section 518
Section 518.2190Â Finishes
a)Â Â Â Â Â Â Â Â Cubicle and window curtains and draperies shall be
noncombustible or flame retardant and shall pass both the large- and small-scale
tests of NFPA 701.
b)Â Â Â Â Â Â Â Â Flame spread and smoke developed ratings of finishes shall be
in accordance with NFPA 101.
c)Â Â Â Â Â Â Â Â Floor materials shall be easily cleanable and have wear
resistance appropriate for the location involved. Floors in toilets, janitor's
closets and similar areas shall be water resistant. In all areas frequently
subject to wet cleaning methods, floor materials shall not be physically
affected by germicidal and cleaning solutions.
d)Â Â Â Â Â Â Â Â Wall bases in soiled workrooms and other areas that are
frequently subject to wet cleaning methods shall be made integral and coved
with the floor, tightly sealed to the wall, and constructed without surface
voids that can harbor vermin.
e)Â Â Â Â Â Â Â Â All wall finishes shall be washable and, in the immediate area
of plumbing fixtures, shall be smooth and moisture resistant. Walls in spaces
subject to frequent cleaning shall be of suitable materials.
f)Â Â Â Â Â Â Â Â Floor and wall penetrations by pipes, ducts, and conduits
shall be tightly sealed to minimize entry of vermin, smoke and fire. Joints of
structural elements shall be similarly sealed.
g)Â Â Â Â Â Â Â Â Ceilings shall be cleanable and shall have a finished surface
that covers all overhead duct work and piping. Finished ceilings may be
omitted in mechanical and equipment spaces, shops, general storage areas, and
similar spaces, unless required for fire-resistive purposes.
h)Â Â Â Â Â Â Â Â The following areas shall have acoustical ceilings:
1)Â Â Â Â Â Â Â Â Corridors in patient areas,
2)Â Â Â Â Â Â Â Â Nurses' stations, and
3)Â Â Â Â Â Â Â Â Waiting areas.