77 Ill. Adm. Code 518.2200
Structural Requirements
Section 518
Section 518.2200Â Structural
Requirements
a)Â Â Â Â Â Â Â Â In addition to compliance with this Part, all applicable local
or State building codes and regulations shall be observed.
b)Â Â Â Â Â Â Â Â The buildings and all parts thereof shall be of sufficient
strength to support all dead, live, and lateral loads without exceeding the
working stresses permitted for the materials of their construction in generally
accepted good engineering practice.
c)Â Â Â Â Â Â Â Â Special provision shall be made for machines or apparatus
loads that would cause a greater load than the specified minimum live load.
d)Â Â Â Â Â Â Â Â Consideration shall be given to structural members and
connections of structures that may be subject to earthquakes or tornadoes.Â
Floor areas where partition locations are subject to change shall be designed
to support for the partition, a uniformly distributed load of 25 p.s.f.
e)Â Â Â Â Â Â Â Â Construction shall be in accordance with NFPA 101 and the
minimum requirements contained in this Part.
1)Â Â Â Â Â Â Â Â Foundations shall rest on natural solid ground and shall be
carried to a depth of not less than one foot below the estimated frost line or
shall rest on leveled rock or load-bearing piles or caissons when solid ground
is not encountered. Footings, piers and foundation walls shall be adequately
protected against deterioration from the action of ground water. Test borings
shall be taken to establish proper soil-bearing values for the soil at the
building site.
2)Â Â Â Â Â Â Â Â Assumed live load shall be in accordance with the International
Building Code.
f)Â Â Â Â Â Â Â Â Chapter 18, New Health Care Occupancies, of NFPA 101 shall
apply in its entirety.