77 Ill. Adm. Code 890.745
Dental Units
Section 890.745 Dental Units
a) A
reduced pressure principle backflow preventer assembly conforming to ASSE 1013,
or a fixed air gap, shall be installed on each dental unit or group of dental
units.
b) Dental
vacuum systems connected to the water supply shall be provided with backflow
protection.
c) If a
dental unit has a water outlet below the flood rim level of a cuspidor, then an
approved reduced pressure principle backflow preventer assembly, a fixed air
gap, an air vent hole on the outlet, or an approved vacuum breaker shall
protect the water supply from each dental unit.