77 Ill. Adm. Code 820.210
Swimming Facility Water Treatment System
Section 820
Section 820.210 Â Â Swimming Facility
Water Treatment System
a)Â Â Â Â Â Â Â Â General Requirements
1)Â Â Â Â Â Â Â Â A water treatment system, consisting of pumps, piping,
filters, water conditioning, disinfection equipment and other accessory
equipment shall be provided to clarify, chemically balance and disinfect the
swimming pool water. The system shall be designed for a recirculation flow rate
that will result in a turnover period in each pool not exceeding those
specified below. Systems serving pools with skimmers shall be designed for a
flow rate of at least 30 gallons per minute for each skimmer.
Type
of Pool
Maximum Turnover Period
Diving
Pools
8 Hours
Wading
Pools, Wading Areas
2 Hours
Plunge Pools and Plunge Areas for Water Slides
2 Hours
Lazy Rivers
2 Hours
Other Pools
6 Hours
Spas
30 Minutes
2)Â Â Â Â Â Â Â Â Other than equipment for circulating, heating, filtering and
chemically treating water, as specified in this Section, or for automation of
water quality control, no other type of device may be used as part of a pool
water treatment system.
b)Â Â Â Â Â Â Â Â Pumping Equipment
1)Â Â Â Â Â Â Â Â The recirculation pump shall deliver the flow necessary to
obtain a turnover as specified in subsection (a). A valve for regulating the
rate of flow shall be provided in the recirculation pump discharge piping.
2)Â Â Â Â Â Â Â Â The pump shall provide a minimum backwash rate of 15 gallons
per minute per square foot of filter area in sand filter systems. The pump
shall supply the required recirculation rate at a total dynamic head of at
least 50 feet for all vacuum filters, 70 feet for pressure sand or cartridge
filters, or 80 feet for pressure diatomaceous earth filters, unless a lower
head is shown by the designer to be hydraulically appropriate.
3)Â Â Â Â Â Â Â Â If the pump operates with static suction lift, it shall be
self-priming.
4)Â Â Â Â Â Â Â Â Where vacuum filters are used, a vacuum limit switch shall be
provided on the pump suction line. The vacuum limit switch shall be set for a
maximum vacuum of 18 inches of mercury.
5)Â Â Â Â Â Â Â Â A compound vacuum-pressure gauge shall be installed on the
pump suction line as close to the pump as possible. A vacuum gauge may be used
for pumps with suction lift. A pressure gauge shall be installed on the pump
discharge line adjacent to the pump, with no valves between the pump and the
gauge. Gauges shall be installed where they can be easily read.
6)        Hair and Lint Strainer. A hair and lint strainer shall be
installed on the suction side of the pump except on vacuum filter systems. The
strainer basket shall be easily removable. Valves shall be installed to allow
the flow to be shut off during cleaning, switching baskets, or inspection.
c)        Water Heater. A water heater shall be installed at all indoor
pools. Pool water heaters shall be installed in accordance with the
manufacturer's recommendations.
1)Â Â Â Â Â Â Â Â The heater piping system shall be equipped with a valve bypass
pipe around the heater, sized for the swimming pool design flow rate.  The
influent and effluent heater piping shall be valved, and shall conform to
material specifications as approved for water distribution applications in the
Illinois Plumbing Code.
2)Â Â Â Â Â Â Â Â A heating coil, pipe or steam hose shall not be installed in a
swimming pool.
3)Â Â Â Â Â Â Â Â Thermometers shall be provided in the piping to check the
temperature of the water returning from the pool and the temperature of the
blended water returning to the pool.
4)Â Â Â Â Â Â Â Â The design of the water heating system shall prevent the
introduction of water in excess of 115° F. to the pool.
5)Â Â Â Â Â Â Â Â A pressure relief valve with a maximum pressure rating of 75
pounds per square inch and having a thermal capacity at least equal to the heat
input rating of the heater shall be provided, with the discharge piped to
within 6 inches of the floor.
6)Â Â Â Â Â Â Â Â Gas or other fuel-burning water heaters shall be vented to the
outdoors.
7)Â Â Â Â Â Â Â Â Heaters for indoor pools shall be capable of maintaining a
minimum pool water temperature of 76° F.
8)Â Â Â Â Â Â Â Â Combustion and ventilation air shall be provided for fuel-burning
water heaters as required by the heater manufacturer.
9)Â Â Â Â Â Â Â Â Heaters for indoor swimming pools shall be sized on a basis of
150 British Thermal Units (BTU) per hour input per square foot of pool water
surface area.
(1 kilowatt = 3,412 BTU/hr.)
10)Â Â Â Â Â Â Â Â Heat exchangers used to heat pool water by use of a toxic
transfer fluid, as defined in Section 890.120 of the Illinois Plumbing Code,
shall be of double-wall construction, with the space between the two walls
having a drain open to the atmosphere.
d)Â Â Â Â Â Â Â Â Flow Meter. Flow meters shall be located so that the rate of
recirculation and the backwash rate of sand filters can be read. In a multiple
pool system, flow meters shall be provided for each pool. Separate flow meters
shall be provided to monitor the flow for each area of a pool with a turnover
rate that differs from adjacent areas according to subsection (b)(1). Flow
meters shall be provided on inlet supply piping in accordance with subsection (f)(2)(G).Â
Flow meters shall be installed on a straight length of pipe with no valves,
elbows or other sources of turbulence within 10 pipe diameters upstream or 5
diameters downstream from the flow meters. (See Appendix A.Illustration G.)
e)Â Â Â Â Â Â Â Â Vacuum Cleaning System
1)Â Â Â Â Â Â Â Â A vacuum cleaning system capable of reaching all parts of the
pool floor shall be provided.
2)Â Â Â Â Â Â Â Â When
the vacuum cleaning system is an integral part of the pool recirculation
system, the wall fitting shall connect to the suction side of the pump ahead of
the hair and lint strainer. Vacuum outlets in pools shall be equipped with
covers that automatically close and latch when the vacuum hose is removed. A
shut-off valve shall be installed in the piping. The suction outlet fitting
shall comply with IAPMO SPS.
f)Â Â Â Â Â Â Â Â Piping, Skimmer and Overflow System
1)Â Â Â Â Â Â Â Â Piping
A)Â Â Â Â Â Â Â The pool recirculation piping shall comply with Section
890.Appendix A.Table A of the Illinois Plumbing Code for water service pipe or
water distribution pipe.
B)Â Â Â Â Â Â Â The piping shall be designed to carry the required flow at
velocities not exceeding 5 feet per second in suction piping, and 10 feet per
second in pressure piping, unless greater velocities can be hydraulically
provided. Gravity piping shall be sized so that the head loss in piping,
fittings, valves, etc., does not exceed the head available during normal
operating conditions.
C)Â Â Â Â Â Â Â The following waste lines shall be provided with 6-inch air
gaps at their points of discharge to the waste sump or sewer:
i)Â Â Â Â Â Â Â Â Â Main
drain bypass or other connections to waste;
ii)Â Â Â Â Â Â Â Â Sub-surface drains or deck drains around a pool that
discharge to a sanitary or combined sewer;
iii)Â Â Â Â Â Â Â Filter
backwash or drain lines and overflow lines;
iv)Â Â Â Â Â Â Â Surge
tank drain and overflow lines;
v)Â Â Â Â Â Â Â Â Pump
discharge to waste lines; and
vi)Â Â Â Â Â Â Â Gutter
bypass to waste lines.
2)Â Â Â Â Â Â Â Â Inlets
A)Â Â Â Â Â Â Â Inlets for filtered water shall be located and directed to
produce uniform circulation of water to maintain a uniform disinfectant
residual throughout the entire pool without the existence of dead spots, and to
produce surface flow patterns that effectively assist skimming. In pools with
skimmers, inlets installed where the water depth is 18 inches or more shall be
installed in the pool wall at a depth of 8 inches to 16 inches below the
mid-point on the skimmer throat. Each inlet installed in a wall of a pool
where skimmers are used shall be directional.
B)Â Â Â Â Â Â Â The velocity of flow through any inlet orifice shall be in the
range of 5 to 20 feet per second, except that in pools equipped with skimmers
it shall be in the range of 10 to 20 feet per second. Velocities for various
flows are shown in Appendix B.Table C.
C)Â Â Â Â Â Â Â Inlets installed in pool walls shall be spaced as follows:
i)Â Â Â Â Â Â Â Â Â In the shallow end wall, each inlet shall serve a linear
distance of no more than 8 feet. In the deep end wall, each inlet shall serve
a linear distance of not more than 15 feet.
ii)Â Â Â Â Â Â Â Â In pools with a water surface area greater than 1,500 square
feet or length in excess of 60 feet, additional inlets shall be provided along
side walls at no more than 15-foot intervals.
iii)Â Â Â Â Â Â Â The location of inlets in pools with skimmers may vary from
the requirements of this subsection (f)(2)(C) to allow locations that will
assist in skimming.
D)Â Â Â Â Â Â Â At least one inlet shall be located in each recessed stairwell
or other space where water circulation might be impaired.
E)Â Â Â Â Â Â Â Where floor inlets are used, inlets shall be uniformly spaced
at a distance of no greater than 20 feet apart, and rows of inlets shall be
within 15 feet of each side wall. Floor inlets shall be flush with the pool
floor and shall include a diffuser plate to evenly distribute the flow in all
directions.
F)Â Â Â Â Â Â Â Â Floor inlets are required in wading areas that are more than
30 feet in width.
G)Â Â Â Â Â Â Â If both wall and floor inlets are used in a swimming pool, the
wall inlets and the floor inlets shall be supplied by separate piping, with
valves and flow meters installed in each so that the flow can be individually
regulated and monitored.
3)Â Â Â Â Â Â Â Â Outlets
A)Â Â Â Â Â Â Â Each
pool shall be provided with a main drain system installed at the deepest point,
which shall be connected to the pool recirculation system. For
multiple-purpose pools, with a floor consisting of more than one drainage area,
at least one drain shall be provided in each basin, so that each portion of the
pool floor is sloped to drain.
B)Â Â Â Â Â Â Â Main drains shall be spaced not less than 3 feet apart, nor
more than 30 feet apart, nor more than 15 feet from side walls, and shall be
connected in parallel.
C)Â Â Â Â Â Â Â A hydrostatic relief valve shall be provided for in-ground
pools.
D)Â Â Â Â Â Â Â Main drain piping shall be sized for removal of the water
through it at a rate of at least 100 percent of the design recirculation flow
rate. The piping system shall be valved to permit adjustment of flow through
it.
E)Â Â Â Â Â Â Â If the pool cannot be drained completely through the main
drain, a portable pump that will effect complete pool drainage shall be
provided.
F)Â Â Â Â Â Â Â Â Each
outlet, including main drains and suction outlets, but not including skimmers,
shall be covered with a certified safety cover having openings not exceeding ½
inch that is not removable without the use of tools or meets the requirements
of subsection (f)(3)(K). The water flow rate through certified safety covers
shall not exceed the maximum flow rate recommended by the manufacturer.
G)Â Â Â Â Â Â Â Suction
outlets shall be equipped with a certified safety cover with dimensions of at
least 18 by 23 inches or 29 inches diagonally, or the suction system shall
include a minimum of two hydraulically balanced outlets spaced at least 3 feet
apart, center to center. In a spa, the two outlets may be installed closer
than 3 feet apart if installed on different surfaces, e.g., one outlet in the
floor and one in a wall.
H)Â Â Â Â Â Â Â For
systems with multiple suction outlets, the sum of the maximum flow rates for
the covers shall be at least twice the system maximum flow rate. This
requirement shall not apply to systems in which each suction outlet is at least
18 inches by 23 inches or 29 inches as measured diagonally.
I)Â Â Â Â Â Â Â Â A
suction outlet shall not be installed on a horizontal surface of a stair or
seat.
J)Â Â Â Â Â Â Â Â Suction
outlets and certified safety covers shall be installed in accordance with the
manufacturer's requirements. For suction outlets with field-fabricated sumps
or other sumps not specified by the manufacturer of a certified safety cover
installed on the outlet, there shall be a spacing of at least 1½ pipe diameters
between the outlet pipe or fitting and the bottom of the cover.
K)Â Â Â Â Â Â Â Field-fabricated
suction outlets that are at least 18 inches by 23 inches in size shall be
certified for compliance with ANSI/APSP 16 by a professional engineer licensed
to practice in Illinois. The Licensed Professional Engineer shall provide
documentation of the testing and a certification document to the property
owner. The Licensed Professional Engineer shall certify a maximum flow rate
for each outlet. Copies of all documentation shall be retained on the swimming
facility premises for inspection by the Department.
L)Â Â Â Â Â Â Â The
following documentation is required to certify a field-fabricated suction
outlet for compliance with the ANSI/APSP 16 standard:
i)Â Â Â Â Â Â Â Â Â The
suction fitting shall not protrude from the installed surface more than 2
inches.
ii)Â Â Â Â Â Â Â Â The maximum
allowable flow through the cover shall be calculated and specified.
iii)Â Â Â Â Â Â Â The
maximum system flow rate for the pool pump shall be specified.
iv)Â Â Â Â Â Â Â The
design of a field-fabricated suction outlet shall be specified by a licensed
engineer to fully address the considerations of cover/grate loadings;
durability; hair, finger and limb entrapment issues; cover/grate secondary
layer of protection; related sump design; and other features specific to the
site.
v)Â Â Â Â Â Â Â Â Field-fabricated
suction outlets shall have the following information specified by the licensed
engineer: compliance with ANSI/APSP 16; statement of single or multiple drain
use; maximum certified flow rate; installed life of the fitting in years;
installation position of the outlet (wall or floor); and instructions on
installation and service for the fitting.
4)Â Â Â Â Â Â Â Â Perimeter Overflow Systems
A)Â Â Â Â Â Â Â Pools that have a width exceeding 30 feet shall have a
continuous perimeter overflow system.
B)Â Â Â Â Â Â Â A perimeter overflow system shall:
i)Â Â Â Â Â Â Â Â Â Extend completely around the pool except that interruptions
not exceeding 25 percent of the pool perimeter nor 30 feet each may be allowed
for steps, water slide entries, and side walls adjacent to zero-depth edges;
ii)Â Â Â Â Â Â Â Â Permit
inspection, cleaning, and repair;
iii)Â Â Â Â Â Â Â Be designed so that no ponding or retention of water occurs;
iv)Â Â Â Â Â Â Â Be designed to prevent the entrapment of bather's arms, legs
and feet;
v)Â Â Â Â Â Â Â Â Except at a zero-depth edge, have an overflow lip that
provides a good handhold and is level to within â…› inch. At a zero-depth
edge, a trench drain covered with a slip-resistant grating installed flush with
the pool deck and with the pool floor, and level to within â…› inch
measured along the pool perimeter, shall be provided;
vi)Â Â Â Â Â Â Â Provide for the removal of all surface debris skimmed from the
pool;
vii)Â Â Â Â Â Â Be designed for removal of water from the pool surface at a
rate of at least 100 percent of the design turnover flow rate;
viii)Â Â Â Â Â Discharge
to the recirculation system;
ix)Â Â Â Â Â Â Â Be provided with drains and piping that will not allow the
overflow channel to become flooded when the pool is in use; and
x)Â Â Â Â Â Â Â Â Have drain gratings with open area at least equal to two times
the area of the outlet pipe and that can be removed for cleaning.
C)       Surge Capacity. Perimeter overflow systems shall be provided
with a surge capacity of at least 0.6 gallon per square foot of pool water
surface area. Surge capacity shall be provided either in a vacuum filter tank,
a surge tank, or combination of vacuum filter tank and surge tank. Valving
shall be provided to maintain the proper operating water level in the pool.
5)        Skimmers. Skimmers are permitted on pools where the width
does not exceed 30 feet. If skimmers are provided, the following shall be met:
A)Â Â Â Â Â Â Â At least one skimmer shall be provided for each 500 square feet
of water surface area or fraction of that area;
B)Â Â Â Â Â Â Â Skimmers shall be located to optimize skimming;
C)Â Â Â Â Â Â Â Each skimmer and piping shall be designed to be capable of
providing a flow-through rate of not less than 30 gallons per minute;
D)Â Â Â Â Â Â Â Skimmers shall be piped to provide approximately equal flow
through each skimmer;
E)Â Â Â Â Â Â Â The surface skimmer piping shall have a valve to permit
adjustment of flow through it;
F)Â Â Â Â Â Â Â Â If an equalizer pipe is installed, the skimmer shall be
equipped with a valve that will restrict flow through the equalizer pipe during
normal operation of the skimmer. The equalizer pipe shall be connected to the
main drain pipe;
G)Â Â Â Â Â Â Â The skimmer shall be tested in accordance with NSF Standard 50
and listed by an approved certification agency;
H)Â Â Â Â Â Â Â Skimming devices shall be built into the pool wall;
I)Â Â Â Â Â Â Â Â A basket that can be removed without the use of tools, and
through which all overflow water must pass, shall be provided; and
J)Â Â Â Â Â Â Â Â The skimmer shall be provided with a floating weir and shall
operate at variations in water level over a range of at least 4 inches.
g)        Make-up Water. Make-up water shall be added through a fixed
air gap of at least 6 inches to the pool, surge tank, vacuum filter tank, or
other receptacle. When make-up water is added directly to the pool, the
fill-spout shall be located under a low diving board or immediately adjacent to
a ladder rail, grab rail, or fixed lifeguard chair. There shall be no
connection between a therapy pool or associated water treatment system and a
swimming pool or its recirculation system.
h)Â Â Â Â Â Â Â Â Filtration
1)Â Â Â Â Â Â Â Â Filters shall be certified to comply with NSF Standard 50 and
listed by an approved certification agency. The design filtration rate in the
particular application in which the filter is used shall not exceed the maximum
design filtration rate for which the filter was certified. An official
certification label from the certifying agency shall be permanently affixed to
the filter.
2)Â Â Â Â Â Â Â Â Pressure gauges that indicate the inlet and outlet pressures
of pressure filters shall be installed.
3)Â Â Â Â Â Â Â Â For pressure filters, an observable free-fall discharge, sight
glass or other means of determining the clarity of backwash water shall be
provided.
4)Â Â Â Â Â Â Â Â Overflow piping shall be connected to vacuum filters if the
rim of the filter tank is below the pool water level. Drain piping for vacuum
filter tanks shall be provided.
5)Â Â Â Â Â Â Â Â The backwash rate for sand filters shall be at least 15
gallons per minute per square foot of filter area. A lesser backwash rate may
be allowed when air scouring is used in accordance with the filter
manufacturer's specifications.
6)Â Â Â Â Â Â Â Â A filter backwash disposal facility, designed so that
flooding, overflowing or excessive splashing does not occur when the filter is
backwashed at the required flow rate, shall be provided where filters designed
to be backwashed are used.
7)Â Â Â Â Â Â Â Â A filter pre-coat pot or funnel shall be installed on the pump
suction piping when diatomaceous earth filters are used, unless a pre-coat pot
is provided as an integral part of the filter. The filter piping shall allow
recycling or disposal of filter effluent during the pre-coating operation.
8)Â Â Â Â Â Â Â Â If continuous feeding of diatomaceous earth is used with a
vacuum diatomaceous filter to permit a design filtration rate higher than would
otherwise be allowable, equipment capable of feeding diatomaceous earth at a
rate of at least 1.5 ounces per day per square foot of filter area shall be
provided.
9)Â Â Â Â Â Â Â Â Filter media for sand filters shall be as specified by the
filter manufacturer.
10)Â Â Â Â Â Â Â Â Prior to disposal, wash or backwash water from diatomaceous
earth filters shall be passed through a separation tank designed for removal of
suspended diatomaceous earth and solids.
i)Â Â Â Â Â Â Â Â Â Chemical Feeders
1)Â Â Â Â Â Â Â Â Equipment Capacity
A)       Chlorine. Equipment for supplying chlorine or chlorine
compounds shall be of sufficient capacity to feed chlorine at a rate of 8 parts
per million (p.p.m.) for outdoor pools and three parts per million for indoor
pools, based on the flow rate required by the table in subsection (a). Feed
rates for various chlorinators and solutions are shown in Appendix B.Table D.
B)       Bromine. Equipment for supplying bromine shall be capable of
delivering at least 15 p.p.m. for outdoor pools and 5 p.p.m. for indoor pools
based on a minimum design flow rate as required by the table in subsection (a).
C)Â Â Â Â Â Â Â Ozone
i)Â Â Â Â Â Â Â Â Â Ozone may be used as a supplement to chlorination or
bromination as required in subsection (i)(1). Ozone-generating equipment and
its components shall be tested in accordance with NSF Standard 50 and listed by
an approved certification agency.
ii)Â Â Â Â Â Â Â Â The ambient air ozone concentration shall be less than 0.10
p.p.m. in the vicinity of the ozonator and at the pool water surface. Ambient
ozone monitors shall be installed in the equipment room, in the vicinity of the
ozone-generating equipment, and, when the ozonation system is used at an indoor
swimming pool facility, in the swimming pool enclosure. Audible and visual
alarms that are activated by ozone concentrations in excess of .10 p.p.m. shall
be connected to the ozone monitor. The ozone-generating equipment shall
automatically shut off when the ozone concentration in the air exceeds 0.30
p.p.m. or when the pool recirculation flow is interrupted.
iii)Â Â Â Â Â Â Â All corona discharge systems shall include a method for
removing ozone in the water in excess of 0.1 p.p.m. prior to return to the
pool.
2)        Positive Displacement Pumps (Hypochlorinators). Positive
displacement pumps that are used to inject the disinfectant solution into the
recirculation line shall be of variable flow type, shall be of sufficient
capacity to feed the amount of disinfectant required by subsection (i)(1), and
shall be installed so that feeding of chemicals is interrupted whenever the
swimming pool recirculation flow is interrupted. Positive displacement pumps
for feeding chlorine compounds or chemicals for control of pH shall be
certified by a certified laboratory to conform to NSF Standard 50. If calcium
hypochlorite is used, the concentration of calcium hypochlorite in the solution
shall not exceed 5 percent by weight. The solution container shall have a
minimum capacity equal to the volume of solution required per day at the feed
rate required in subsection (i)(1).
3)Â Â Â Â Â Â Â Â Gas Chlorinators
A)Â Â Â Â Â Â Â The chlorine supply and gas-feeding equipment shall be housed
in a separate, relatively air-tight room with an out-swinging door. The room
shall be provided with an exhaust system that takes its suction not more than 8
inches from the floor and discharges outdoors in a direction to minimize
exposure to toxic fumes. The fan shall be capable of producing one air change
per minute. Openings such as filters or grill openings at a high point
opposite the exhaust fan intake shall be provided for introducing a fresh air
supply to the enclosure. The intake to the make-up air supply shall be located
where the discharge from the exhaust system will not be drawn back into the
room. The room shall have a window with an area of at least 100 square inches
and shall have artificial lighting. Electrical switches for lighting and
ventilation shall be outside and adjacent to the door. Scales for weighing
chlorine cylinders in service shall be provided.
B)Â Â Â Â Â Â Â The chlorine-feeding device shall be designed so that gas feed
is automatically terminated during interruptions of the flow of the water
supply. In addition, the release of chlorine shall be terminated when the
recirculation pump is shut off. Where other than swimming pool recirculated
water is used, the supply line shall be equipped with an electric shutoff valve
wired to the recirculation pump and shall be equipped with a suitable backflow
preventer. (See Appendix A.Illustrations L and N for methods of installation.)
C)Â Â Â Â Â Â Â Chlorinator vent lines shall terminate outdoors. A screen made
from a chlorine-resistant material shall be installed where the vent line
terminates outdoors to exclude insects.
D)Â Â Â Â Â Â Â The gas chlorinator shall be the solution feed type capable of
delivering chlorine at its maximum rate without releasing chlorine gas to the
atmosphere.
E)Â Â Â Â Â Â Â The water supply for the gas-feeding equipment shall produce
the flow rate and pressure required according to the manufacturer's
specifications for proper operation of the equipment.
4)        pH Control Feeders. At pools with a volume greater than
100,000 gallons, or pools using gas chlorine as a disinfectant, a chemical feed
system shall be installed to maintain the pH of pool water within the range of
7.2 to 7.6. The system shall be installed so that the feeding of the pH
controlling chemical is automatically interrupted whenever the swimming pool
recirculation flow is interrupted. A solution tank of at least 15 gallons
capacity shall be provided and shall be marked as containing a chemical to control
pH. Alternatively, a system incorporating a cylinder of carbon dioxide and
injecting mechanism may be employed to lower pH.
5)Â Â Â Â Â Â Â Â Erosion-Type Chemical Chlorine Feeders
A)Â Â Â Â Â Â Â Erosion type chlorine and bromine feeders shall be tested in
accordance with NSF Standard 50 and listed by an approved certification agency.
B)Â Â Â Â Â Â Â Only the chemical specified by the feeder manufacturer shall be
used as the disinfecting agent.
C)Â Â Â Â Â Â Â Erosion type chemical feeders shall be installed in accordance
with the equipment manufacturer's instructions.
6)        Copper/Silver and Copper Ion Generators. All copper/silver
and copper ion generators shall be tested in accordance with NSF Standard 50
and listed by an approved certification agency and may be used only as a
supplement to chlorination or bromination as required in subsection (i)(1).