77 Ill. Adm. Code 855.520
Reestablishment of the Work Area and HVAC Systems in Schools
Section 855
Section 855.520Â
Reestablishment of the Work Area and HVAC Systems in Schools
The contractor shall reestablish
the work area in accordance with the following procedure:
a)Â Â Â Â Â Â Â Â Reestablishment of the work area shall only occur following
the completion of the cleanup procedures and after clearance air monitoring has
been performed and documented to the satisfaction of the school board or
building owner.
b)Â Â Â Â Â Â Â Â The contractor and building owner shall visually inspect the
work area for any remaining visible residue. Evidence of contamination shall
necessitate additional cleaning in accordance with Section 855.465.
c)Â Â Â Â Â Â Â Â Additional air monitoring shall be performed in accordance
with Section 855.470 if additional cleanup is necessary.
d)Â Â Â Â Â Â Â Â Following completion of clearance air monitoring of the work
area in accordance with Section 855.470, remaining polyethylene barriers and
worker and equipment decontamination enclosure systems shall be removed and
disposed of as asbestos-contaminated waste. Following removal, the entire
area, including HVAC filter assembly and duct work, shall be wet cleaned or
HEPA vacuumed to remove residual asbestos fibers.
e)Â Â Â Â Â Â Â Â Mounted objects removed from former positions during area
preparation activities may be resecured.
f)Â Â Â Â Â Â Â Â Objects that were removed to temporary locations may be
relocated to original positions.
g)Â Â Â Â Â Â Â Â New filters shall be installed in HVAC systems, and mechanical
and electrical systems shall be reestablished in working order.