77 Ill. Adm. Code 870.160
Natural and Liquefied Petroleum Gas Installation
Section 870.160Â Natural and Liquefied Petroleum Gas
Installation
a)Â Â Â Â Â Â Â Â Natural
Gas. There are three codes affecting the operation of natural gas facilities
in manufactured homes:Â the Pipeline Safety Regulations administered by the
U.S. Department of Transportation for the pipeline to the meter; the National
Fuel Gas Code written by the National Fire Protection Association for the
piping from the meter to underneath the home, and the Manufactured Home
Construction and Safety Standards, administered by the Department of Housing
and Urban Development for the appliance installation, operation and venting in
the home.
1)Â Â Â Â Â Â Â Â Piping.Â
Natural gas piping must be of approved materials.
A)Â Â Â Â Â Â Â Plastic
piping approved for natural gas, ASTM 2513, must be installed below ground
level, except that it may terminate aboveground if:
i)Â Â Â Â Â Â Â Â Â The
aboveground part of the plastic service line is protected against deterioration
and external damage; and
ii)Â Â Â Â Â Â Â Â The
plastic service line is not used to support external loads. Plastic pipe,
tubing and fittings shall be joined in accordance with manufacturer's
instructions. An electrically continuous corrosion resistant tracer wire
(Minimum 14 AWG (American wire gauge)) or tape shall be buried with the plastic
pipe to facilitate locating.
B)Â Â Â Â Â Â Â Metallic
pipe shall be at least standard weight, Schedule 40. Copper and brass pipe
shall not be used if the gas contains more than an average of 0.3 grains of
hydrogen sulfide per 100 standard cubic feet of gas. Metallic tubing such as
seamless copper (ASTM A254) shall be permitted to be used with gas not
corrosive to such material.
2)Â Â Â Â Â Â Â Â Support.Â
All piping under the home must be supported with appropriate hangers spaced at
no more than 6 foot intervals for 1 inch diameter or less pipe and no more than
10 foot intervals for piping 1¼ inch in diameter or more.
3)Â Â Â Â Â Â Â Â Defects
and Corrosion. Defects in pipe, tubing or fittings shall not be repaired.Â
When defective pipe, tubing or fittings are located in a system, the defective
material shall be replaced. Gas piping in contact with earth or other material
that could corrode the piping shall be protected against corrosion in an
approved manner.
4)Â Â Â Â Â Â Â Â Meters,
Valves and Regulators. Meters and regulators must be installed in a readily
accessible location and be protected from corrosion and other damage. Each
service line must have a service line valve located upstream of the regulator
or meter.
5)Â Â Â Â Â Â Â Â Location
and Testing. Each buried main must be installed with at least 24 inches of
cover and service lines with at least 18 inches of cover. The service line
cover can be reduced to 12 inches if external damage to the pipe is not likely
to result. The gas piping system must be tested for leaks prior to occupancy
of the home.
b)Â Â Â Â Â Â Â Â Liquefied
Petroleum Gas (LP). LP gas containers must be approved for the intended use
and properly located in accordance with the Standard for the Storage and
Handling of Liquefied Petroleum Gases (NFPA 58-98) (Table 9 − Proper
Location of Liquified Petroleum Gas Containers).
c)Â Â Â Â Â Â Â Â Oil
Burning Equipment. Fuel oil burning equipment must be installed in accordance
with the Standards for the Installation of Oil Burning Equipment (NFPA 31).