77 Ill. Adm. Code 890.1340
Determination of Sizes for Drainage System
Section 890
Section 890.1340Â
Determination of Sizes for Drainage System
a)        Maximum Fixture Unit Load. The maximum number of DFUs that
may be connected to a given size of building drain, horizontal branch, or
vertical soil or waste stack is established in Appendix A.Tables G and H. Exception:
As an alternative to using Appendix A.Tables G and H to design and size the
building drain, horizontal branch, or vertical soil or waste stack, the system
may be designed and sized employing current engineering practices, provided
that the design/plans are signed and sealed by an Illinois licensed
professional engineer, an Illinois licensed architect or an individual
Certified in Plumbing Design (CPD) by the American Society of Plumbing
Engineers and approved in writing by the Department.
b)Â Â Â Â Â Â Â Â Minimum Size of Building Drain, Horizontal Branches, Drainage
Piping
1)Â Â Â Â Â Â Â Â The minimum size of any gravity building drain shall be 4
inches in diameter.
2)Â Â Â Â Â Â Â Â Pressure-building drains shall not be used where gravity drains
may be installed. Pressure-building drains shall be sized in accordance with
the ejector pump manufacturer's recommendation, but shall not be less than 2
inches in diameter.
3)Â Â Â Â Â Â Â Â Gravity drained horizontal branches of the building drain
shall be sized in accordance with Appendix A.Table H.
4)Â Â Â Â Â Â Â Â No portion of the drainage system installed underground or
below a basement or cellar shall be less than 2 inches in diameter. Â The
venting system is excluded from this requirement.
5)Â Â Â Â Â Â Â Â The drainage piping shall not be reduced in size in the
direction of flow.
c)        Minimum Size of Soil and Waste Stacks. No soil or waste stack
shall be smaller than the largest horizontal branch connected to the stack,
except that a 4 inch by 3 inch water closet connection shall not be considered
as a reduction in pipe size.
d)        Waste Stacks Serving Kitchen Sinks. In one- or two-family
dwellings in which the waste stack or vent receives the discharge of a
kitchen-type sink and also serves as a vent for fixtures connected to the
horizontal portion of the branch served by the waste stack, the minimum size of
the waste stack up to the highest sink branch connection shall be 2 inches in
diameter. Above that point the size of the stack shall be governed by the
total number of drainage fixture units vented by the stack. (See Appendix J.Illustration
F.)
e)        Future Fixtures. If the future installation of fixtures is
provided for during initial construction, the fixtures provided for shall be
considered in determining the required size of drain pipes and vent piping.Â
Piping provided for future installation of fixtures shall be terminated with a
plugged fitting or fittings at the stack so as to form no dead ends. In a
multi-story building, when openings are roughed in for future fixtures below
the uppermost level, properly sized vent piping shall be connected to the vent
system and carried down to the appropriate lower level and be capped or plugged
in an accessible location for venting of the future fixtures.