77 Ill. Adm. Code 890.1350
Offsets in Drainage Piping
Section 890
Section 890.1350Â Offsets in
Drainage Piping
a)        Offsets of 45 Degrees or Less. An offset in a vertical soil
or waste stack with a change of direction of 45 degrees or less from the
vertical shall be sized as a straight vertical stack. If a horizontal soil or
waste branch connects to the soil or waste stack within two (2) feet above or
below the offset, a relief vent shall be installed in accordance with Section
890.1550(c). (See Appendix J: Illustration G.)
b)        Offsets of More Than 45 Degrees. A soil or waste stack with
an offset of more than 45 degrees from the vertical shall be sized and
installed as follows:
1)Â Â Â Â Â Â Â Â The portion of the stack above the offset shall be sized as
for a regular stack based on the total number of drainage fixture units above
the offset.
2)        The offset shall be sized as for a building drain. (See
Appendix A:Â Table G.)
3)Â Â Â Â Â Â Â Â The portion of the stack below the offset shall be sized as
for the offset or based on the total number of drainage fixture units on the
entire stack, whichever is larger. (See Appendix A: Table L.)
4)Â Â Â Â Â Â Â Â The drain offset shall have a relief vent installed as
provided in Section 890.1550. In no case shall a horizontal soil or waste
branch connect to the soil or waste stack within two (2) feet above or below
the drain offset. (See Appendix J: Illustration H.)
c)        Above Highest Branch. An offset above the highest horizontal
waste branch is an offset in the stack vent and shall be considered only as it
affects the developed length of the vent. (See Appendix J: Illustration I.)
d)        Below Lowest Branch. In the case of an offset in a soil or
waste stack below the lowest horizontal branch, no change in diameter of the
stack shall be required because of the offset if it is made at an angle of not
greater than 45 degrees. If such an offset is made at an angle greater than 45
degrees, the required diameter of the offset and the stack below it shall be
determined as for a building drain. (See Appendix A: Table G, and Appendix
J:Â Illustration J.)