77 Ill. Adm. Code 890.1420
Stack Vents, Vent Stacks, Main Vents
Section 890
Section 890.1420Â Stack
Vents, Vent Stacks, Main Vents
a)        Design. A properly designed and installed venting system, in
conjunction with the soil or waste system, is essential to protect trap seals
and prevent siphonage, aspiration, or back pressure. The venting system shall
be designed and installed to permit the admission or emission of air so that
under normal and intended use the seal of any fixture trap shall never be
subjected to a pneumatic pressure differential of more than a 1-inch water
column. All fixture traps shall be protected by the use of a vent or venting
system constructed in accordance with this Part.
b)        Installation. Fixture traps shall be protected by the
appropriate method as follows: an individual dry vent, a wet vent, a common
vent, a circuit or loop vent, an island vent, or a combination waste and vent
system. A stack vent or vent stack shall be installed with a soil or waste
stack whenever vents, relief vents or other branch vents are required. (See
Appendix K.Illustration A.)
c)        Main Vent. Each building in which plumbing is installed shall
have at least one main vent no smaller than 3 inches for each building drain
installed. (See Appendix A.Table K and Appendix K.Illustration C.)