77 Ill. Adm. Code 890.1430
Vent Terminals
Section 890
Section 890.1430Â Vent
Terminals
a)Â Â Â Â Â Â Â Â Vent Terminals. Vents shall terminate independently above the
roof to the outside atmosphere or shall be connected to another vent at least 6
inches above the flood‑level rim of the highest fixture served by the vent.Â
(See Appendix K.Illustration B.)
b)        Roof Extensions. Extensions of vent pipes through a roof
shall be terminated at least 12 inches above the roof unless a roof is to be
used for any purpose other than weather protection. If a roof is to be used for
any purpose other than weather protection, the vent shall be extended at least 7
feet above the roof. (See Appendix K.Illustration D.)
c)        Flashings. Each vent terminal shall be made water-tight with
the roof by proper flashing.
d)        Location of Vent Terminal. No vent terminal from a drainage
system shall be directly beneath a door, window, overhang or other ventilating
intake opening of the building, nor shall any vent terminals be within 12 feet
horizontally of an opening or within 4 feet of a vertical obstruction unless it
is at least 2 feet above the top of the opening. (See Appendix K.Illustration
E.)
e)        Extensions Outside Building. No soil, waste or vent pipe
extension (except for vent terminals as provided in subsections (b) and (d) of
this Section() shall be located on the outside of a wall of any building, but
shall be installed inside the building. Wet vents located within an exterior
wall or in a wall adjacent to an unheated space shall be protected from
freezing.
f)Â Â Â Â Â Â Â Â Flag
poles. Vent terminals shall not be used for the purpose of supporting flag
poles, television aerials, or similar purposes.
g)Â Â Â Â Â Â Â Â Vent
Terminal Size. Each vent extension through the roof shall be a minimum of 3
inches in diameter and no smaller than the vent that it terminates. Vent
terminals shall not be screened.
h)Â Â Â Â Â Â Â Â Increasers.
Changes in size or diameter of vent terminals shall be made by the installation
of an increaser commencing at least 1 foot below the roof.