77 Ill. Adm. Code 890.1470
Fixture Trap Vents
Section 890
Section 890.1470Â Fixture
Trap Vents
a)Â Â Â Â Â Â Â Â Distance
of Trap From Vent. Each fixture trap shall have a protecting vent located so that
the developed length in the fixture drain from the trap weir to the vent
fitting is within the requirements in Appendix A.Table I. (See Appendix K.Illustration
L.)
b)Â Â Â Â Â Â Â Â Trap
Weir. The vent pipe opening from a soil or waste pipe, except for water
closets or fixtures with an integral trap, shall not be below the trap weir.Â
(See Appendix K.Illustration N.)
c)Â Â Â Â Â Â Â Â Crown
Vent. No trap vent shall be installed within two pipe diameters of the trap
weir. (See Appendix K.Illustration M.)
d)Â Â Â Â Â Â Â Â Hydraulic
Gradient. Fixture drains shall be vented within the hydraulic gradient between
the trap outlet and the junction with another drain. The hydraulic gradient as
applied to a gravity drain and its corresponding vent connection is interpreted
as the grade line. (See Appendix A.Table I and Appendix K.Illustration N.)
e)Â Â Â Â Â Â Â Â Different
Level. If any stack has fixtures entering at different levels, the fixtures
other than the fixtures entering at the highest level shall be vented in
accordance with Section 890.1420(b).
f)Â Â Â Â Â Â Â Â Fixture
Trap Protection. Each fixture trap shall be protected by the appropriate
method as follows:Â an individual dry vent, a wet vent, a common vent, a
circuit or loop vent, an island vent or a combination waste and vent system.
g)Â Â Â Â Â Â Â Â Mechanical
Vents. Mechanical devices shall not be installed in lieu of vent piping.
h)Â Â Â Â Â Â Â Â Trap
Seal Loss. Trap seal that is subject to loss by evaporation shall be
prevented. (See Section 890.410(f).)