77 Ill. Adm. Code 890.1520
Circuit and Loop Venting
Section 890
Section 890.1520Â Circuit and
Loop Venting
a)        Battery Venting. A soil or waste branch to which two but not
more than eight of the same type of floor outlets or fixtures, such as eight water
closets, eight pedestal urinals, eight shower stalls or eight floor drains are
connected in battery, may be vented by a circuit vent that shall take off from
in front of the last fixture connection. Blowout type fixtures are
prohibited. Lower floor branches serving more than three water closets shall
be provided with a relief vent taken off in front of the first fixture
connection. The horizontal branch for its full length to the farthest fixture
opening shall be uniformly sized based on the total drainage fixture load as
listed in Appendix A.Tables G, H and L. (See Appendix K.Illustration Y.)
b)        Dual Branches. When parallel horizontal branches serve a
total of eight water closets (four on each branch), each branch shall be
provided with a relief vent at a point between the two water closets most
distant from the soil stack. The horizontal branch for its full length to the
farthest fixture opening shall be uniformly sized based on the total drainage
fixture load as listed in Appendix A.Tables G, H and L. Intermediate floor
branches shall be provided with a relief vent taken off in front of the first
fixture connection. If traps other than water closets discharge above the
horizontal branch, each such trap shall be provided with a continuous vent.Â
(See Appendix K.Illustration Z.)
c)        Vent Connections. When the circuit or relief vent connections
are taken off the horizontal branch, the vent branch connection shall be taken
off vertically from the top of the horizontal branch. (See Appendix K.Illustration
AA.)
d)        Fixtures Back-to-Back in Battery. When fixtures are connected
to one horizontal branch through a double wye, a sanitary cross in a vertical
position, or a manufactured fixture carrier, a common vent for each two fixtures
back-to-back shall be provided. (See Appendix K.Illustration BB.)
e)        Fixture Connections. Branch wastes and fittings for circuit
vented fixtures shall be installed so that the fixture drain enters the side of
the branch drain. (See Section 890.1320(i) and Appendix K.Illustrations Y and
CC.)
f)        Circuit and Loop Vented Fixtures. For circuit and loop vented
fixtures are installed in a multi-story building, a relief vent shall be
provided at the base connection into the horizontal by connecting the vent
stack, full-size, into or near the base of the soil stack, or by connecting the
vent stack directly into the horizontal branch near the soil stack. The vent
shall be carried full size. (See Appendix K.Illustration DD.)