77 Ill. Adm. Code 890.1530
Pneumatic Ejectors
Section 890
Section 890.1530Â Pneumatic
Ejectors
An air pressure relief vent from
a pneumatic ejector shall not be connected to the regular venting system but
shall be connected separately to the outside atmosphere terminating as required
in Section 890.1430 for vent extensions through roofs. Such relief pipe shall
be of sufficient size to relieve air pressure inside the ejector to atmospheric
pressure within ten (10) seconds, but shall not be smaller than one and
one-half (1 1/2) inches in diameter.