77 Ill. Adm. Code 890.520
Gasoline, Oil and Flammable Liquids
Section 890
Section 890.520Â Gasoline,
Oil and Flammable Liquids
a)Â Â Â Â Â Â Â Â Commercial vehicle repair garages, gasoline stations with
grease racks or pits, and oil change facilities shall be provided with floor
drains or trench drains connected to a gas and oil interceptor. If these
facilities are connected to a private sewage disposal system, the floor or
trench drains shall be connected to a holding tank in lieu of a gas and oil
interceptor in accordance with the Private Sewage Disposal Licensing Act.Â
Where trench drains are used to carry wastes to a gas and oil interceptor, the
trench drain shall either extend the entire length of the work area or shall be
installed in each working stall. For all facilities specified in this Section
in which floor drains are installed, a minimum of one floor drain per working
stall or one floor drain for each 500 square feet shall be installed.
b)Â Â Â Â Â Â Â Â Commercial and residential vehicle storage areas greater than
1,000 square feet with floor or trench drains installed shall comply with subsection
(c)(1), (2) or (3). Exception: residential garages with fewer than five
vehicle bays are exempted from this requirement.
c)Â Â Â Â Â Â Â Â All facilities, other than those specified in subsection (a),
that generate fuel, oil or flammable waste shall meet one of the following
requirements:
1)Â Â Â Â Â Â Â Â provide
floor drains or trench drains connected to a gas and oil interceptor.
2)Â Â Â Â Â Â Â Â provide floor or trench drains connected to a holding tank in
lieu of a gas and oil interceptor when these drains are connected to a private
sewage disposal system.
3)Â Â Â Â Â Â Â Â provide an alternative system approved by the Department (i.e.,
an oil reclamation system or containment area).
d)Â Â Â Â Â Â Â Â General Requirements
1)Â Â Â Â Â Â Â Â Gas and oil interceptors shall be of cast iron, steel, polyethylene,
polymer concrete or equally durable fiberglass materials suitable for gas and
oil. Fiberglass interceptors shall not be used for receiving any substance
other than gas and oil. Poured concrete interceptors are prohibited.
2)Â Â Â Â Â Â Â Â Each gas and oil interceptor or basin shall be provided with a
heavy metal cover, which shall be bolted into place and made gas and -water-tight.
3)Â Â Â Â Â Â Â Â Each gas and oil interceptor and, if provided with separate
compartments, each compartment and basin shall be provided with a vent of at
least 2 inches, which shall extend independently to the outer air. Two or more
vents may be connected to a header, which shall be 6 inches or higher than the
lowest floor or trench drain served.
4)Â Â Â Â Â Â Â Â The inlet of the gas and oil interceptor or the first basin
shall be trapped except when floor drains are individually trapped.
5)Â Â Â Â Â Â Â Â Floor drains above the level of the gas and oil interceptor or
basins shall connect to a stack vent extending independently to the outer air.
6)Â Â Â Â Â Â Â Â Gas and oil interceptors must be constructed in accordance
with the Illinois State Fire Marshal's rules and regulations for underground
storage tanks (41 Ill. Adm. Code 174, 175, 176, 177), when applicable, and
shall be maintained to prevent loss of gas, oil, etc. Gas and oil interceptors using
an automatic draw off feature shall have a separate U.L. approved underground
storage tank or storage tank installed integral with the interceptor.
7)        Minimum Dimension. Gas and oil interceptors shall have a
depth of at least 2 feet below the invert of the discharge drain.
8)        Performance. The gas and oil interceptor shall have at least
a 12-inch water seal with a minimum 90 percent efficiency rating or have a minimum
of an 18-inch water seal. Gas and oil in the effluent from the gas and oil interceptor
or triple basin shall not exceed the levels specified by the sewage treatment
authority having jurisdiction, in accordance with local ordinances and
regulations.
9)Â Â Â Â Â Â Â Â Poured concrete trench drains are prohibited for gas and oil discharges.
e)Â Â Â Â Â Â Â Â Aircraft hangars used exclusively for storing aircraft shall
be exempt from this Section under the following conditions:
1)Â Â Â Â Â Â Â Â No operation of aircraft or maintenance of any kind,
including, but not limited to, mechanical work upon an aircraft, or aircraft fueling,
oiling, lubricating or washing, may be performed in the hangar.
2)Â Â Â Â Â Â Â Â Oil, gasoline or flammable materials of any kind shall not be
stored in the hanger.
3)Â Â Â Â Â Â Â Â The hangar shall not be provided with floor drains or trench drains.
4)Â Â Â Â Â Â Â Â The hangar shall not contain drains of any kind that are
connected to a public sewer/private sewage disposal system/holding tank.
5)Â Â Â Â Â Â Â Â In lieu of the requirements of subsections (e)(1) through (4),
aircraft storage hangars may install floor drains or trench drains that comply
with the requirements of subsections (a) through (e).
f)Â Â Â Â Â Â Â Â Sizing
1)Â Â Â Â Â Â Â Â The minimum size interceptor for all facilities required to
comply with subsection (a) shall be 6 cubic feet (45 gallons) for the first 500
square feet of floor area plus 1 cubic foot per each additional 500 square feet
to be drained into the interceptor.
2)Â Â Â Â Â Â Â Â The minimum size interceptor for all facilities, except those
facilities required to comply with subsection (a), shall be 6 cubic feet (45
gallons) for the first 3,000 gross square feet plus 1 cubic foot per each
additional 1,000 square feet to be drained into the interceptor. Floor area for
parking decks or garages shall be determined by the gross square feet of the
parking spaces.