77 Ill. Adm. Code 890.530
Special Waste Interceptors
Section 890
Section 890.530Â Special
Waste Interceptors
a)        Catch Basins. In all motor vehicle wash racks, drainage shall
discharge into a water-tight catch basin at least 36 inches in diameter, or 3
feet by 2½ feet (rectangular shape). The bottom shall not be less than 27
inches below the invert of the outlet pipe. The outlet pipe shall be trapped
with a catch basin trap and shall be constructed of cast iron or schedule 40
plastic with a trapseal of at least 6 inches and a cleanout of at least 4
inches in diameter.
b)Â Â Â Â Â Â Â Â Commercial laundries shall be equipped with an interceptor
having a removable wire basket or similar device that will prevent materials
detrimental to the sewage system from passing into the system.
c)Â Â Â Â Â Â Â Â Sand, bottle and slaughter houses that will produce wastes
that either settle or float (Example: oil or grease from meat packing operations,
bottling establishments or heavy solids.) shall have an interceptor installed that
complies with Section 890.510(a).
d)        Interceptor for Special Waste. Before installing any
interceptor for any other flammable or special wastes, a drawing including all
pertinent information shall be submitted to the Department for approval.