83 Ill. Adm. Code 460.410
Sample Testing Procedures
Section 460
Section 460.410 Sample
Testing Procedures
a) An MSP that chooses to use sample testing shall use the
procedures prescribed in any of the following documents (alone or in
combination) to sample test non-demand, self-contained single-phase or
three-wire network meters.
1) ANSI/ASQC Z1.4-1993 "Sampling Procedures and Tables for
Inspection by Attributes", approved 1993, American Society for Quality
Control, 611 East Wisconsin Avenue, Milwaukee WI 53202. No later amendment or
editions are incorporated.
2) ANSI/ASQC Z1.9-1993 "Sampling Procedures and Tables for
Inspection by Variables for Percent Nonconforming", approved 1993,
American Society for Quality Control, 611 East Wisconsin Avenue, Milwaukee WI
53202. No later amendment or editions are incorporated.
b) The MSP shall divide the meter population into homogeneous
groups consisting of meters of the same basic type and purpose. All meters
within each homogeneous group shall be eligible for sampling each time a sample
is taken. A sample shall be taken each year from each homogeneous group, and
testing shall be completed during the same calendar year. The size of each
sample shall be determined through use of an allowed sampling procedure listed
in subsection (a).
c) The
performance of a homogeneous group shall be considered acceptable when, after
applying the performance criteria described in subsection (f) to each meter
included in the sample, the sample indicates an acceptable quality level (AQL)
at least as stringent as 2.5%. AQL shall indicate the maximum percentage of
nonconforming meters to be permitted within a homogeneous group.
d) Each MSP shall perform 100% testing on all used or
remanufactured meters purchased.
e) Each
MSP using sample testing shall file a yearly report no later than March 31 of
the following year with the Chief Clerk of the Commission and provide a copy to
the Manager of the Energy Division or its successor detailing the sample plan
used in the previous year, along with the results of the testing program
f) The
performance of a meter that is tested as part of a sample shall be considered
acceptable when its average percent registration, prior to any adjustment, is
not less than 98% or more than 102%. The average percent registration for each
meter shall be calculated as described in Section 460.370(d).
g) All
tests described in Section 460.370(a) shall be performed on all meters included
in the sample, and all meters included in the sample shall be left adjusted so
that the error shall not exceed the limits listed in Section 460.370(b).
h) When
an MSP finds the performance of any homogeneous group to be unacceptable
through sample testing, the MSP shall perform corrective action on the group.
Corrective actions outlined in this subsection shall be completed by the end of
the second calendar year after the year in which the homogeneous group
performance is initially found to be unacceptable. The corrective action shall
consist of one of the following:
1) Removal
of a subgroup of problem meters from service so that the performance of the
remaining meters in the group is found to be acceptable through subsequent
sample testing; or
2) Removal
from service of all meters associated with the group.