83 Ill. Adm. Code 466.75
Limited-Export and Non-Exporting Distribution Energy Resources Facilities
Section
466.75 Limited-Export and Non-Exporting Distribution Energy Resources
Facilities
The following technical specifications are
intended to identify acceptable export control methods to facilitate the
interconnection and parallel operation of limited-export and non-export systems
with the EDC's electric distribution system.
a) If a DER facility
uses any configuration or operating mode in subsections (c)(1) through
(
6) to limit the
export of electrical power across the point of interconnection, then the export
capacity shall be only the amount capable of being exported (not including any
inadvertent export). To prevent impacts on system safety and reliability, any
inadvertent export from a DER facility must comply with the limits identified
in this Section. The export capacity specified by the interconnection customer
in the application will subsequently be included as a limitation in the
interconnection agreement. Applicants seeking to interconnect using the
operating modes under this Section shall submit proposed control or protection
settings in their application for review by the EDC to verify compliance with
the requirements of this Section.
b) The export
control types and settings listed in subsection (c) are acceptable for
controlling export capacity unless the EDC identifies and communicates to the
customer during the interconnection screening or study process specific impacts
that affect the reliability, safety, operation and power quality of the EDC's
system associated with the protection relays, settings and control schemes
listed in this Section. In that case, the EDC may identify alternate settings
that would be required for safe and reliable interconnection of the proposed DER
facility. The EDC may also identify any monitoring and control equipment to be
installed at Applicant’s expense on DER systems using export control equipment
that is required for safe and reliable interconnection and operation of the DER
facility.
c) The export
controls identified in subsections (c)(1) through (3) are acceptable for
non-exporting systems only. The export control identified in subsections (c)(4)
and (c)(5) may be used for limited export systems only. The export controls in subsections
(c)(6) and (7) may be used for either non-exporting or limited export systems.
Inverter-based limited export systems shall use advanced inverters utilizing
operating modes and settings specified by the EDC in its written technical
standards for interconnection.
1) Reverse Power
Protection (Device 32R)
To limit export of power across the point
of interconnection, a reverse power protective function is implemented using a
utility-grade protective relay. The default setting for this protective
function shall be 0.1% (export) of the service transformer's nominal base
nameplate rating, with a maximum 2.0 second time delay to limit inadvertent
export.
2) Minimum Power
Protection (Device 32F)
To limit export of power across the point
of interconnection, a minimum import protective function is implemented using a
utility-grade protective relay. The default setting for this protective
function shall be 5% (import) of the generating unit's total nameplate
capacity, with a maximum 2.0 second time delay to limit inadvertent export.
3) Relative Distributed
Energy Resource Rating
This option requires the DER facility's
nameplate capacity to be so small in comparison to its host facility's minimum
load that the use of additional protective functions is not required to ensure
that power will not be exported to the electric distribution system. This
option requires the DER facility's nameplate capacity to be no greater than 50%
of the interconnection customer's verifiable minimum host load over the past 12
months.
For systems above 250 kVA, the EDC
may require additional assurances, equipment, or agreements based upon
evaluation of the stability and reliability of the minimum load data. This
option is not available for interconnections to area networks or spot networks.
4) Directional Power
Protection (Device 32)
To limit export of power across the point
of interconnection, a directional power protective function is implemented
using a utility-grade protective relay. The default setting for this protective
function shall be the export capacity value, with a maximum 2.0 second time
delay to limit inadvertent export.
5) Configured Power
Rating
A reduced output power rating utilizing
the power rating configuration setting may be used to ensure the DER does not
generate power beyond a certain value lower than the nameplate capacity. The
reduced power rating shall be indicated by means of a nameplate rating replacement,
or by a supplemental adhesive nameplate rating tag to indicate the reduced
nameplate rating. At the discretion of the EDC, the applicant may additionally
be required to provide a letter from the manufacturer confirming the reduced
capacity.
6) Limited Export
Utilizing Power Control Systems
The following are the minimum
requirements for the limited export utilizing power control systems that meet
the criteria specified in this subsection (c)(6). Other factors relevant to the
interconnection study process may necessitate additional technical requirements
that are not explicitly noted in this subsection. This option is not available
for interconnections to area networks or spot networks.
A) DER
facilities utilizing this option must use an NRTL-certified UL 1741 power
control system and inverter system with a maximum open loop response time of no
more than 30 seconds for systems less than or equal to 100 kVA and a maximum
open loop response time of no more than 10 seconds for systems greater than 100
kVA. The DER facility must disconnect from the electric distribution system,
ceasing to energize the electric system or halting energy production within 2.0
seconds if the period of continuous export exceeds 30.0 seconds.
B) Failure of
the control system or inverter system for more than 30.0 seconds resulting from
loss of control or measurement signal, loss of control power, single component
failure, or related control sensing of the control circuitry must result in the
DER facility entering non-export operation mode whereby no energy is exported
across the point of interconnection to the electric distribution system until
the customer has reestablished real power output control of the DER facility.
C) An acceptable
open loop response time may need to be mutually agreed upon between the EDC and
the applicant for DER facilities with a nameplate capacity greater than 1 MVA
that utilize a NRTL certified power control system.
COMMISSION NOTE:
NRTL testing to the UL power control system certification requirements decision
shall be accepted until similar test procedures for power control systems are
included in a standard.
7) Limited Export
Using Agreed-Upon Means
DER facilities may be designed with other
control systems or protective functions to limit export and inadvertent export
if mutual agreement is reached with the EDC. The limits may be based on
technical limitations of the interconnection customer's equipment or the
electric distribution system equipment. To ensure inadvertent export remains
within mutually agreed-upon limits, the interconnection customer may use an
uncertified power control system, an internal transfer relay, energy management
system, or other customer facility hardware or software if approved by the EDC.