83 Ill. Adm. Code 501.180
Diaphragm Meters
Section 501.180 Diaphragm Meters
a) A
utility shall install a new diaphragm meter set and revisions to an existing
diaphragm meter set in accordance with the recommendations of ANSI B109.1,
XQ0008 (June 2000) for diaphragm meters with a rated capacity less than 500
cubic feet per hour and in accordance with ANSI B109.2, XQ0009 (June 2000) for
diaphragm meters with a rated capacity of 500 cubic feet per hour or greater.
b) A
utility furnishing natural gas service with diaphragm meters shall ensure the
use of suitable meter proving or testing equipment to determine the accuracy of
the meter. The average accuracy of a diaphragm meter is determined by averaging
the accuracy of the check and open flow rates.
1) The
open rate is 95% to 105% of the rated capacity.
2) The
check rate is 20% to 33% of the rated capacity.
3) The
maximum allowable accuracy spread between the open and check rates' accuracy is
1.0%.
c) A
utility shall conduct periodic accuracy tests on all installed diaphragm meters
at least every 120 months unless the utility has provided notification to the
Commission regarding its plans to conduct sample testing in accordance with
Section 501.250.