83 Ill. Adm. Code 501.190
Rotary Meters
Section 501.190 Rotary Meters
a) A
utility shall install all rotary meters or revisions to existing rotary meter
sets in accordance with the recommendations of ANSI B109.3, XQ0010 (June 2000).
b) A
utility furnishing gas service through a rotary meter shall verify that the
meter's accuracy meets the requirements of Section 501.170(a) before placing
the meter in service.
1) A
utility may rely on the manufacturer's factory accuracy test to demonstrate
that a new rotary meter meets the Section 501.170(a) requirements only if the
utility also conducts quality assurance reviews on its new rotary meters.
2) A
utility that conducts quality assurance reviews must group the new meters into
meter lots consisting of the same size and manufactured under the same
conditions. The utility must then sample test these lots in accordance with a
single sample plan for normal inspection, Inspection Level II, of ANSI/ASQ
Z1.4-2008 using an acceptable quality level not to exceed 1.0%.
3) In
the event that a meter lot fails, the utility must either return the meters to
the manufacturer or test all of the meters in the lot to verify compliance with
Section 501.170(a).
4) A
utility shall retain a record of a meter's accuracy test for the life of the
meter.
c) A
utility shall differential test an in-service rotary type positive displacement
meter at least every 60 months. If the meter's pressure differential for a
given flow rate is more than 50% higher than the utility's initial differential
test or the factory published differential curve, a utility shall return the
differential to a value below the 50% limit. If the utility cannot return the
meter's differential to below the 50% limit, the utility shall clean and retest
the rotary meter within 7 days and, if the meter's pressure differential is
still more than 50% higher than the utility's initial differential test or the
factory published differential curve, the utility will replace the meter within
60 days. If the meter is of sufficient size that portions of a customer's
structure require modification to remove the meter, then the utility will
replace the meter within 90 days unless the utility and customer agree to a
longer period, not to exceed 180 days.
d) If a
utility documents conditions at the meter that prevent the utility from
obtaining a differential reading from the meter, then the utility may delay
verification until those conditions cease to exist or for four months,
whichever is shorter. If a utility delays verification, it shall maintain for
three years documentation of the conditions that prevented verification within
the required 60 months and provide the documentation to an authorized
representative of the Commission when requested.
e) In
lieu of the differential test requirement in subsection (c), a utility may
conduct an accuracy test of a rotary meter. The average accuracy of a rotary
meter is determined by averaging the accuracy of the check and open flow rates.
1) The
check rate is 10% to 33% of the meter's rated capacity.
2) The
open rate is 60% to 105% of the meter's rated capacity. The utility may
substitute the proving equipment's maximum capacity for the open flow rate if
the meter's required testing volume exceeds the utility's testing equipment's
capacity.
f) A
utility shall maintain the most recent 10 years of inspection records, as well
as the dates of all inspections of rotary meters.