83 Ill. Adm. Code 501.300
Correctors
Section 501.300 Correctors
a) A
utility shall install all correctors in accordance with the recommendations of
AGA Gas Measurement Manual, Electronic Corrector, Part No. 15 (May 1999),
XQ9901.
b) A
utility that installs an electronic or mechanical corrector shall verify the
proper operation of the corrector at least every 60 months.
1) Verification
temperatures are 32°F and 75°F/or flowing gas temperature with a tolerance of ±
2.5°F.
2) Verification
pressures are zero and flowing pressure with a tolerance of ± 1%.
c) A utility shall maintain
the most recent 10 years of inspection records.