83 Ill. Adm. Code 501.310
Transmitters
Section 501.310 Transmitters
a) A
utility shall install all transmitters in accordance with the recommendations
of AGA Gas Measurement Manual (Revised), Electronic Flow Computers and
Transducers, Part No. 8 (1988), XQ8805.
b) A
utility that installs digital and analog transmitters for use in conjunction
with flow computers in custody transfer metering shall verify the proper
operation of the transmitters at least every six months.
c) A
utility must verify that its transmitters maintain a tolerance of ± 2.5°F at
flowing gas temperature of the calibrated temperature span. A utility must
verify that its transmitters maintain inspection pressures of zero and
full-calibrated span with a tolerance of 1% of span.
d) A utility shall maintain
the most recent five years of inspection records.