83 Ill. Adm. Code 501.320
Gas Chromatograph
Section 501.320 Gas Chromatograph
a) A
utility shall install all gas chromatographs according to the recommendations
of the device's manufacturer.
b) A
utility shall set all in-service gas chromatographs to perform an automatic
calibration at least once every 24 hours. If the utility is using the
chromatograph to assist the measurement calculation at a utility-owned natural
gas storage facility and the facility is not injecting or withdrawing natural
gas, the utility may suspend the calibration of the chromatograph until the
facility resumes injecting or withdrawing natural gas.
c) A
utility shall perform field verification of all in-service gas chromatographs
at least every 3 months and verify that the un-normalized mole percent variance
is within ± 1.5% of the gas contained within the calibrated gas cylinder.
d) A
utility shall certify or replace the calibrated gas cylinders at least every 36
months.