8 Ill. Adm. Code 2150.215.25
Basic Rules
Section 215
TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE
SUBCHAPTER e: FERTILIZERS
PART 215 ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS, EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.25 BASIC RULES
Section 215.25 Basic Rules
This Section applies to all Sections
of this Part unless otherwise noted.
a) These
provisions shall not be construed as prohibiting the continued use or
reinstallation of containers constructed and maintained in accordance with the
1949, 1950, 1952, 1956, 1959, 1965, 1968, 1971, 1974, 1977, 1980, 1983, 1986,
1989, 1992, 1995 and 1998 editions of the ASME Code or any revisions thereof in
effect at the time of fabrication. Reinstalled stationary pressure vessels with
a design capacity greater than 3000 gallons shall comply with CGA G-2.1,
Section 5.1. If a storage tank is currently being used and does not have a
U-1A form or a build sheet or a legible data plate, it must be taken out of
service by January 1, 2030.
1) Containers
in use or operation on or after July 1, 2016, and any storage vessel that is
not in service within the State of Illinois, or any storage vessel greater than
3000 gallons to be reinstalled, shall comply with one or more of the following:
A) The
storage vessel has been stress relieved during fabrication in accordance with
the Code in effect at the time of fabrication; or
B) The
storage vessel has cold-formed heads that have been heat stress relieved; or
C) The
storage vessel has been fabricated with hot-formed heads.
2) Welded
attachments to pads may be made after post-weld heat treatment. However,
implements of husbandry do not require post-weld heat treatment if they are
fabricated with hot-formed heads or with cold-formed heads that have been
stress relieved.
b) Requirements
for new construction and original test, repair, and alterations of containers
(including USDOT portable tanks), other than refrigerated storage tanks must
comply with the following:
1) Containers
used with systems covered in Sections 215.85, 215.110, and 215.115 shall be
made of steel or other material compatible with ammonia and tested in
accordance with the currently incorporated ASME Code (see Section 215.16). An
exception to the ASME Code requirements is that construction under Table UW 12
at a basic joint efficiency of under 80% is not authorized.
2) Containers
designed and constructed in accordance with the ASME Code, other than
refrigerated storage containers, shall comply with the following additional
requirements:
A) The
entire container shall be postweld heat treated after completion of all welds
to the shells and heads. The method employed shall be as prescribed in the
ASME Code, except that the provisions for extended time at a lower temperature
for postweld heat treatment shall not be permitted. Welded attachments to pads
may be made after postweld heat treatment. Exception: implements of husbandry
will not require postweld heat treatment if they are fabricated with hot-formed
heads or with cold-formed heads that have been stress relieved.
B) Steels
used in fabricating pressure containing parts of a container shall not exceed a
specified tensile strength of 70,000 psi. Exception: implements of husbandry
may be fabricated from steel having a specified tensile strength of 75,000 psi.
C) Containers
shall be inspected by a person who holds a valid National Board Commission.
Exception: refrigerated storage tanks with a design pressure of 15 psig or less
and containers covered in Section 215.90.
D) Repair
or alteration of pressure-containing parts of a container shall be performed in
compliance with the applicable provisions of the current edition of the
National Board Inspection Code. Where specific procedures are not given, it is
intended that, subject to acceptance of the inspector, all repair or alteration
shall conform as much as possible to the ASME Code section and edition to which
the container was constructed.
c) Except
for pneumatic testing, all containers shall only be pressured with ammonia
vapor except for dual usage involving the storage of liquid propane. Any
device used for the introduction of atmospheric air into any part of anhydrous
ammonia storage, transportation or application systems is prohibited. Any
introduction of any substance other than anhydrous ammonia into the closed loop
anhydrous ammonia system shall be approved by the Department prior to
implementation, except when required to comply with the ASME Code or USDOT
regulations.
d) Any
firm that completes any repair or alteration to a pressure vessel or any piping
and associated appurtenances shall be performed by a firm that holds a valid
certificate of authorization, commonly referred to as an R stamp holder.
e) A
written record of all inspections and maintenance shall be kept at the facility
for a period of 5 years or until sold or removed from service.
f) Railroad
car tanks permanently mounted and used for storage of anhydrous ammonia shall
be removed from a service no later than December 1, 2025.
g) Compliance
with the requirements of this Subpart shall be achieved through repairs and
modifications on or before December 31, 2020.
h) Any
storage vessel that does not have a legible data plate or supporting
documentation of the information on the data plate shall be removed from
service if it is decommissioned from the current site.