8 Ill. Adm. Code 2150.215.65
Transfer of Liquids
Section 215
TITLE 8: AGRICULTURE AND ANIMALS
CHAPTER I: DEPARTMENT OF AGRICULTURE
SUBCHAPTER e: FERTILIZERS
PART 215 ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS, EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
SECTION 215.65 TRANSFER OF LIQUIDS
Section 215.65 Transfer of
Liquids
a) If it
is found necessary to dispose of anhydrous ammonia, it shall be discharged into
a vessel containing water sufficient to absorb it. Sufficient water shall be
at least ten parts of water per one part anhydrous ammonia. The anhydrous
ammonia shall be injected into the water as near the bottom of the vessel as
practical. Provision must be made to prevent bleeding of transport and
railroad tank car liquid lines or hoses into the atmosphere when
disconnecting. This shall be done through the use of a wet hose with a shutoff
valve at each end of the hose, by bleeding into water at no greater rate than
one gallon of anhydrous ammonia to 10 gallons of ammonia-free water to prevent
discharge of fumes into the atmosphere, or with a recovery system.
b) A certified
competent attendant shall supervise the transfer of liquids from the time the
connections are first made until the railroad tank car is finally disconnected
or the transport truck is completely unloaded and finally disconnected. Any
time the site is unattended, the railroad tank car shall not be connected to
the unloading riser. During the transfer operations of the transport, chock
blocks shall be so placed as to prevent rolling of the vehicle.
c) Containers
shall be filled or used only upon authorization of owners.
d) Containers
shall be gauged and charged only in the open air or in a building especially
provided for that purpose.
e) Pumps
used for transferring anhydrous ammonia shall be recommended for anhydrous
ammonia service by the manufacturer or documented for such service by the
owner/operator using recognized and accepted good engineering methods.
1) Liquid
pumps may be piston, rotary, centrifugal or regenerative type for 250 psig
working pressure.
2) Positive
displacement pumps shall be equipped with a pressure actuated by-pass valve on
the discharge side of the pump. This valve shall operate to limit the pressure
developed by the pump to the maximum for which the pump is rated. Piping or
tubing sized to carry the full capacity of the pump at the actuation pressure
of this valve shall connect the discharge of this valve with the container from
which ammonia is being pumped. If this line is capable of being closed off by
a valve, an additional by-pass device shall be incorporated in the pump to
by-pass back to the suction port. The pressure actuated by-pass valve and the
return piping or tubing shall be installed in accordance with the pump
manufacturer's recommendations or documented for such service by the
owner/operator using recognized and generally accepted good engineering
methods.
3) A
pressure gauge graduated from at least 0 to 400 psig shall be installed before
the relief valve line on the discharge side of the pump.
4) Centrifugal
or regenerative pumps do not require a bypass valve, but the installation shall
incorporate a line from the discharge side of the pump to the vapor space of
the supplying tank and a shutoff valve shall be installed in this line.
f) Plant
piping shall contain shutoff valves located as close as practical to the pump
connections.
g) Compressors
used for transferring or refrigerating ammonia shall be recommended for ammonia
service by the manufacturer or documented for that service by the
owner/operator using recognized and generally accepted good engineering
methods.
1) Compressors,
except those used for refrigeration, shall be designed for at least 250 psig
working pressure. Crank cases of compressors not designed to withstand system
pressure shall be protected with a suitable pressure relief valve.
2) Plant
piping shall contain shutoff valves located as close as practical to compressor
connections.
3) A
relief valve large enough to discharge the full capacity of the compressor
shall be connected to the discharge before any shutoff valve. The discharging
pressure of this valve shall not exceed 300 psig and shall be installed so that
it will be vented in a safe location if discharged.
4) Compressors,
except those used in refrigeration, shall have pressure gauges graduated from
0-400 psig at suction and discharge.
5) Adequate
means, such as a drainable liquid trap, shall be provided on the compressor
suction to minimize the entry of the liquid into the compressor.
h) Piping
shall be designed not to restrict flow rates to the extent that protective
devices will not function.
i) Dedicated
lines for loading and separate dedicated lines for unloading are recommended. Minimum
protection shall be provided as follows:
1) Loading
systems shall be protected by properly rated excess flow valves or approved
systems to prevent the emptying of the storage containers in the event of
severance of the hose or swivel type piping.
2) The
liquid unloading line shall be protected by a back check valve located within 5
lineal feet of pipe from the bulkhead.
3) The
minimum protection for all bypass lines shall consist of an excess flow valve
and a manual shutoff valve. The bypass shall be located at the highest
elevation of the storage tank.
4) System
piping shall be designed to prevent the introduction of debris that could
impede the action of valves and other components of the piping system. All
systems in operation on or before July 1, 2016 shall be in compliance no later
than December 1, 2017. Any piping system installed after July 1, 2016 shall
comply prior to initiation of any operations.
j) Transport
trucks shall not be utilized for bulk storage of anhydrous ammonia. It must be
transferred into permanent storage of a capacity equal to or greater than the
transport truck.
k) Railway
tank cars must be transferred into permanent storage of a capacity equal to 50%
of the railway tank car.
l) All
storage tank system liquid and vapor valves must be closed and locked during
the time the plant is unattended. Either hose end lock boxes or locking caps
or chains may be used on the risers. In lieu of locking the valves, a security
fence with two gates on opposite sides shall be installed and kept locked
during the time the plant is unattended.
m) The
transfer of anhydrous ammonia from a tank car or transport to any other unit
for the purpose of converting anhydrous ammonia to aqueous ammonia shall only
be done upon a railway spur owned or leased to the operator of the transferring
facility where the railway tank car can be retained for an indefinite period
and where an aqueous converter is installed at a site. The transfer must be
done in one continuous operation. The requirements of Section 215.30 must be
met before the site and facility will be approved by the Department. Approved
anhydrous ammonia installations designed for converting aqueous ammonia must
have sufficient permanent storage to permit continuous and uninterrupted
unloading from railway tank cars or trucks.
n) Provision
must be made to prevent bleeding of transport and rail car liquid lines or
hoses into the atmosphere when disconnecting. This shall be done through the
use of a wet hose with a shutoff valve at each end of the hose, by bleeding
into water at no greater rate than one gallon of anhydrous ammonia to 10
gallons of ammonia-free water to prevent discharge of fumes into the
atmosphere, or with a recovery system.
o) A
certified statement shall be filed on forms furnished by the Department stating
that all the requirements of this Section, safety equipment and requirements of
this Part have been met. This statement must be filed with the Department
before final approval of the facility will be given by the Department. No
operation shall begin until final approval has been issued.
p) The
filling of mobile containers with a capacity of 3000 gallons or less with
anhydrous ammonia is permissible only at a permanent storage facility approved
by the Department for this purpose. Anhydrous ammonia may be transferred from
a cargo tank motor vehicle with a maximum capacity of 6000 gallons into
containers of 3000 gallons capacity or less mounted on farm vehicles or
containers of 6000 gallons mounted on motor-driven applicators. This transfer
operation is limited to rural areas and only on the premises of the consignee.
This transfer operation must meet all safety requirements of Section 215.20.
Department approved anhydrous ammonia meters or on board scales shall be
employed for this operation. Meters or on board scales shall conform with the
Weights and Measures Act [225 ILCS 470] and 8 Ill. Adm. Code 600. The selling
price quotation, actual billing, and reporting to the Department shall be done
in pounds or tons.
q) All
stationary storage installations with systems for filling nurse tanks or cargo
vessels with container capacity of 6000 water gallons or less shall have all
vapor and liquid risers protected against any break resulting from a
pull-away. Each vapor and liquid hose shall be protected with an individually
properly rated excess flow valve, a manual control valve, and a break-away or
shear fitting designed to conform with good engineering practices.
r) Meters
used for the measurement of liquid anhydrous ammonia shall be recommended for
ammonia service by the manufacturer and approved by the Department. When dual
purpose meters are used and when changing from LPG to anhydrous ammonia or vice
versa, it is necessary to adjust the coefficient of the expansion scale to the
proper setting for the product being metered. This adjustment will require the
removal of the Illinois Weights and Measures Seal. Section 42 of the Weights
and Measures Act requires that the person who breaks such seal be registered
pursuant to that Act.
s) Liquid
meters shall be designed for a minimum working pressure of 250 psig.
t) The
metering system shall incorporate devices that will prevent the inadvertent
measurement of vapor.
u) Transferring
of anhydrous ammonia from a DOT cargo tank motor vehicle must comply with Transportation
Regulations (see Section 215.16).
v) Bulkheads
shall provide protection during unloading events and shall be accomplished with
the following good engineering practices:
1) All
valves shall be protected from any possible pull-away incidents while connected
between the mobile container and the transfer station in such a manner that any
break resulting from a pull-away will occur on the hose or swivel-type piping
side of the connection while retaining intact the valves and piping on the
plant side of the connection;
2) Installation
of reinforced concrete and structural steel bulkheads or equivalent anchorage,
strong enough not to break and sufficiently massive not to be uprooted by the
motor vehicle;
3) A
manual shutoff valve shall be installed on the liquid and vapor line and
located at the bulkhead;
4) The
use of approved breakaway devices, specifically designed for this purpose;
5) Bulkhead protection shall not be attached to the container
piers; and
6) At
least one caution sign at the bulk heads shall be permanently displayed instructing
the cargo tank driver to chock the cargo tanks wheels prior to loading or
unloading. The signs shall be of metal or other comparable material, at least
8½ inches high by 11 inches wide, and shall state:
CAUTION
DRIVER
MUST CHOCK WHEELS
The signs shall have a yellow
background and the letters shall be at least 1½ inches in height.