8 Ill. Adm. Code 215.240
Safety Devices
Section 215
Section 215.240 Safety
Devices
a) Every pressure-vented container shall be provided with one or
more safety pressure relief valves. The rate of discharge shall be in
accordance with the provisions of 8 Ill. Adm. Code Section 215.Table E.
b) Container safety pressure relief valves shall be set to
start-to-discharge at a pressure not to exceed 110 percent of the design
pressure of the container.
c) Safety pressure relief valves shall be arranged so the
possibility of tampering will be minimized. If the pressure setting adjustment
is external, the relief valves shall be provided with means for sealing the
adjustment.
d) Shutoff valves shall not be installed between the safety
pressure relief valves or the vacuum relief valve and the container. A safety
relief valve manifold which allows one valve of two, three, four, or more to be
closed and the remaining valve(s) will provide not less than the rate of
discharge to allow the proper cubic feet per minute of air in relation to tank
capacity as shown in 8 Ill. Adm. Code Section 215.Table A.
e) Each safety pressure relief valve and vacuum relief valve used
shall be clearly and permanently marked as follows:
1) The relief setting.
2) The rate of discharge (see 8 Ill. Adm. Code Section 215.Table
E).
3) The manufacturer's name and identification number.
f) Connections for venting, such as couplings, flanges, nozzles,
and discharge lines, to which relief valves are attached, shall have internal
dimensions at least as large in diameter as the relief valve to avoid
restriction of flow through the relief valves.
g) Discharge from safety pressure relief devices of permanent
storage containers shall be directed in such a manner as to prevent any
impingement of escaping gas.