8 Ill. Adm. Code 215.30
Location of Storage Tanks
Section 215
Section 215.30 Location of
Storage Tanks
a) Tanks
shall be located outside of buildings unless the building is especially
constructed for the safe handling and storage of anhydrous ammonia. Permanent
storage shall be located outside of densely populated areas and subject to the
approval of the Department as follows: If located within the corporate limits
of a village, town, or city, written approval of the municipality's governing
body or a county zoning permit shall be submitted to the Department before
tentative approval to begin construction of a permanent storage facility will
be given. The intended storage must be completed and approved by the
Department within one year from the date written tentative approval was given.
Final approval will be given if the facility and equipment complies with this
Part.
b) Containers
shall be located at least 50 feet from a dug well or other source of potable
water.
c) Nurse
tank load out risers and containers for newly approved sites after July 1, 2003
shall be a minimum distance of 200 feet from the property line. Installation
of additional load out risers or containers at sites approved prior to July 1,
2003 shall be a minimum distance of 75 feet from the property line.
d) Container
locations shall comply with the following distance requirements:
Minimum Distance
(feet) from Container
Nominal
capacity of containers (gallons)
Railroad
mainline property
Place of private
or public assembly
Institutional
occupancy
001-3000
100
200
750
over 3000
100
400
1000
e) Offices
or buildings integral to the agrichemical business are exempt from the minimum
distance requirement. Excluded from the distance requirement are those
installations installed prior to July 1, 2003. The Department will approve
replacement storage tanks to be installed. A replacement tank may be of a
larger capacity. Replacement tanks must meet all requirements of this Part with
the exception of subsection (d). The provisions concerning replacement of
tanks applies specifically to installations installed prior to July 1, 2003. Notwithstanding
the other provisions of this Section, the Department shall not require evidence
of a county zoning permit or approval of the municipal governing body in the
case of replacement of anhydrous ammonia storage vessels of equal or lesser
static volume.
f) A
nurse tank of not more than 3000 gallons or less than 1000 gallons water
capacity may be used as temporary storage in instances where anhydrous ammonia
is used in the manufacturing of liquid or suspension fertilizers provided that
written approval of the municipality’s governing board or a county zoning
permit shall be submitted to the Department before site approval will be
given. Approval will be given based upon compliance with the requirement of
this subsection (f). The distance of the temporary storage nurse tank shall
not be less than 50 feet from the property line or source of drinking water,
not less than 200 feet from existing places of private or public assembly, or
not less than 750 feet from any place of institutional occupancy. The draw bar
must be securely fastened to an anchoring device so as to render the nurse tank
immovable while being used in the manufacturing of fertilizer. During the time
the site is unattended, all liquid and vapor valves must be plugged or capped.
g) Container
storage areas shall be accessible to emergency vehicles and personnel.
h) Storage
container areas shall be maintained clear of dry grass and weeds and other
combustible materials.