8 Ill. Adm. Code 215.35
Markings of Non-Refrigerated Containers and Systems other than DOT Containers
Section 215
Section 215.35 Markings of
Non-Refrigerated Containers and Systems other than DOT Containers
a) Each
system nameplate shall be made of a non-corroding metal permanently attached to
the system by continuous welding around its perimeter and located so as to be
readily accessible for inspection. Nameplates shall be maintained in legible
condition and include markings as prescribed.
b) Each
container or system covered in Sections 215.85, 215.90, 215.110 or 215.115
shall be marked as follows:
1) With
a mark identifying compliance with and other markings required by the Code
under which the container is constructed, with the capacity of the container in
pounds or gallons (U.S. Standards), with the working pressure in psig for which
the container is designed, and with the thickness of the shell and heads.
2) With
the name and address of the supplier of the system or the trade name of the
system and the date of manufacture. This information shall appear on the
system nameplate for aboveground containers.
3) With
markings indicating the maximum level to which the container may be filled with
liquid at temperatures between 20°F and 100°F, except on containers provided
with fixed maximum level indicators or that are filled by weighing. Markings shall
be in increments of not more than 20°F and shall appear on the system nameplate
or on the liquid level gauging device on both underground and aboveground
containers. Refrigerated storage tanks shall be exempt from these requirements
but shall be marked to show the maximum permissible liquid level (see Section
215.60).
4) With
the overall length and outside diameter of the container.
c) All
main operating valves on permanently installed storage containers having a
capacity of over 3000 water gallons shall be identified to show whether the
valve is in liquid or vapor service. The method of identification shall be by
label or color code as follows:
1) Label:
The label LIQUID (or LIQUID VALVE) or VAPOR (or VAPOR VALVE), as appropriate,
shall be placed on or within 12 inches of the valve by means of a stencil tag
or decal; or
2) Color
Code: Liquid valves shall be painted orange and vapor valves shall be painted
yellow. The legend ORANGE − LIQUID or YELLOW − VAPOR shall be
displayed in a conspicuous place at each operating point utilized for loading
or unloading at each permanent storage location. The legend shall have letters
at least two inches high and shall be placed against a contrasting background.
d) Containers
manufactured after January 1, 2003 shall bear a National Board of Boiler and
Pressure Vessel Inspectors stamp indicating registration of the container with that
organization.