8 Ill. Adm. Code 215.40
Tank Appurtenances
Section 215
Section 215.40 Tank
Appurtenances
a) All tanks
and appurtenances of each system shall be approved by the Department prior to
initiation of operations, including the receipt of anhydrous ammonia.
b) All
appurtenances shall be designed for no less than the maximum working pressure
of the portion of the system on which they are installed. All appurtenances
shall be fabricated from materials proved suitable for anhydrous ammonia
service.
c) All
connections to containers except connections for pressure relief devices,
thermometer well, liquid level gauging devices, or connections fitted with No.
54 (0.055 inches) drill size orifice or those plugged shall have shutoff valves
located as close to the container as practical.
d) Excess
flow valves or approved systems shall close automatically at the rated flows of
vapor or liquid as specified by the manufacturer. The piping, including valves
and fittings in the same flow path as the excess flow valve, shall have a
greater capacity than the rated flow of the excess flow valve or approved
system.
e) Liquid
level gauging devices that require bleeding of the product to the atmosphere
and that are so constructed that outward flow will not exceed that passed by a
No. 54 (0.055 inches) drill size opening need not be equipped with excess flow
valves.
f) An
opening in a container to which a pressure gauge connection is made need not be
equipped with an excess flow valve if the opening is not larger than No. 54
(0.055 inches) drill size.
g) Each
facility shall provide the minimum protection at each non-refrigerated storage
tank opening utilized for the transfer of product as follows:
1) The
installation of an:
A) internal
valve in the tank with a manual shutoff valve located immediately outside of
the opening; or
B) approved
excess flow valve or a back check valve inside of the tank, a manual shutoff
valve located immediately outside of the opening and an approved emergency shutoff
valve (ESV) located within 3 feet of the opening side of the manual shutoff
valve.
2) Approved
ESVs or internal valves shall incorporate a reliable actuation system that will
close all of the ESVs or internal valves of the piping system on the first
attempt in the event of emergency or of testing from a remote location. A
minimum of 2 remote actuation devices shall be located no less than 25 feet
reasonably opposed to each other.
3) If
using a pressure source for activation of the ESVs or internal valves, nitrogen,
compressed air or carbon dioxide is deemed acceptable. If using compressed air
as a pressure source, the air shall be clean and kept at a moisture level that
will not prevent the system from operating. Propane or other flammable
materials shall be prohibited for use to activate an ESV or an internal valve.
4) ESVs
and internal valves shall be tested annually for the
functions required. A record of each test result shall be kept at the facility
for a minimum of 5 years.
h) Excess
flow valves shall be designed with a by-pass, not to exceed a No. 60 (0.040
inches) drill size opening, to allow equalization of pressure.
i) All
excess flow valves shall be plainly and permanently marked with the name or
trademark of the manufacturer, the catalog number, and the rated capacity.
j) Each
filling connection on non-refrigerated containers shall have a positive shutoff
valve in conjunction with either an approved internal back-pressure check valve
or an approved internal excess flow valve. Vapor connections on
non-refrigerated containers shall have a positive shutoff valve together with
an approved internal excess flow.