8 Ill. Adm. Code 215.55
Safety Relief Devices
Section 215
Section 215.55 Safety Relief
Devices
a) Every
container used in systems covered by Sections 215.85, 215.110, and 215.115
without permanent supply piping to another source of excess pressure shall be
protected from excess pressure by one or more pressure relief valves of the
spring loaded type conforming with applicable requirements of ASME UG-125(c)(3),
UL-132 or other equivalent pressure relief valve standard.
b) Pressure
relief valves shall be in direct communication with the vapor space of the
container. All pressure relief discharge openings shall have suitable rain
caps that will allow free discharge of the vapor and prevent the entrance of
water. Provision shall be made for draining condensate that may accumulate.
c) The
discharge from pressure relief valves shall be vented away from the container,
upward and unobstructed to the atmosphere.
d) Container
relief device pressure shall be set to discharge at no more than 125% maximum
allowable working pressure for containers built by the 1949 ASME Code Sections
U-68 and U-69, and no more than 100% for those built by all subsequent ASME
Codes. Set pressure tolerance is +10% to 0% for non-refrigerated containers.
e) Pressure
relief valves used on containers covered by Sections 215.85, 215.110 and
215.115 shall be constructed to discharge at not less than the rates required
in Appendix B before the pressure is in excess of 121% of the maximum allowable
working pressure of the container. Relief protection for any other reason
shall use ASME UG-125 through UG-136.
f) Pressure
relief valves shall be so arranged that the possibility of tampering will be
minimized. If the pressure setting adjustment is external, the relief valves
shall be provided with means for sealing the adjustment.
g) Shutoff
valves shall not be installed between the pressure relief valves and the
containers or systems covered by Sections 215.85, 215.110 and 215.115.
h) Relief
valves shall be installed in a manifold that has a required rate of discharge
and so installed to allow either of the pressure relief valves to be closed off
but does not allow both pressure relief valves to be closed off at the same
time, or other suitable device so that they can be replaced while the container
remains pressurized. Containers designed with internal pressure relief systems
are exempt from this requirement.
i) Each
pressure relief valve used with systems covered by Sections 215.85, 215.110 and
215.115 shall be plainly and permanently marked as follows:
1) With
the letters "AA" or the symbol "NH
3
";
2) The
pressure in psig at which the valve is set to start-to-discharge;
3) The
rate of discharge of the valve in cubic feet per minute of air at 60°F and
atmospheric pressure;
4) Year
of manufacture; and
5) The
manufacturer’s name and catalog number.
j) Piping
or connections on either the upstream or downstream side shall not restrict the
flow capacity of the relief valve.
k) The
manufacturer or supplier of a pressure relief valve manifold shall publish
complete data showing the flow rating through the combined assembly of the
manifold with pressure relief valves installed. The manifold flow rating shall
be determined by testing the manifold with all but one valve discharging. If
one or more openings have restrictions not present in the remaining openings,
the restricted opening or openings, or those having the lowest flow, shall be
used to establish the flow rate marked on the manifold nameplate. The marking
shall be similar to that required in Section 215.55 for individual valves.
l) A
hydrostatic relief valve, venting into the atmosphere at a safe location, shall
be installed in each section of piping (including hose) in which liquid can be
isolated between shutoff valves to relieve pressure that could develop from the
trapped liquid. If an equivalent pressure relieving device is used, the maximum
accumulative pressure possible within the system shall not exceed the limits of
the system.
m) The
discharge opening from any pressure relief valve shall not terminate inside any
building or below the highest roof line of the building.
n) A
pressure relief device shall be subject to a systematic, periodic, visual
external inspection at least annually to determine that it:
1) Meets
the applicable requirements specified in this Section;
2) Is
free of evidence of tampering, damage, corrosion or foreign matter that might
prevent proper operation;
3) Is
free of leakage when subject to pressures below the minimum allowable
start-to-discharge setting;
4) Has a
properly installed rain cap or other device to avoid entry of moisture or other
matter into the relief valve outlet; and
5) Has
an open weep hole to permit moisture to escape.
o) Any
deficiency as may be found in subsection (n) shall require immediate corrective
action, replacement or repair of the pressure relief device as may be
appropriate.
p) No
container pressure relief device shall be used over 5 years past the
manufactured date. Records shall be maintained that identify each container
and indicate the date of installation for the pressure relief devices. If no
date is specified, a pressure relief valve shall be replaced no later than five
years following the date of its manufacture or last repair unless it has first
been disassembled, inspected, repaired and tested by the manufacturer, or by a
qualified repair organization, in a manner such that the valve's condition and
performance is certified as being equivalent to the standards for the original
valve. The data regarding repairs or reassembly shall be indicated by stamping
the body or attaching a tag pertaining to the valve with the month and year to
replace or recertify. All facilities shall be in compliance with this subsection
no later than December 31, 2020.