8 Ill. Adm. Code 215.50
Hose Specifications
Section 215
Section 215.50 Hose
Specifications
a) Hose
used in ammonia service and subject to container pressure shall conform to ARPM
IP-14. Dual usage hoses for propane and anhydrous ammonia shall be prohibited.
b) Hose
subject to container pressure shall be designed for a minimum working pressure
of 350 psig and a minimum burst pressure of 1750 psig. Hose assemblies, when
made up, shall be capable of withstanding a test pressure of 500 psig.
c) Hose
and hose connections located on the low-pressure side of flow control, or
pressure-reducing valves on devices discharging to atmospheric pressure, shall
be designed for the maximum low-side working pressure. All connections shall
be designed, constructed and installed so that there will be no leakage when
connected. Shutoff valves on the end of liquid and vapor transfer hoses shall
be equipped with bleed valves to enable the operator to bleed off pressure
prior to disconnecting the hoses except when using minimum loss valve.
d) When
a liquid transfer hose is not drained of liquid upon completion of transfer
operations, that hose shall be equipped with an approved shutoff valve at the
discharge end. Provision shall be made to prevent excessive hydrostatic
pressure in the hose.
e) On
all hose 0.5 inch O.D. and larger used in ammonia service and subject to
container pressure, there shall be etched, cast or impressed at 5 ft. intervals
on the outer hose cover the following information:
Anhydrous Ammonia
XXX psig (Maximum
Working Pressure)
Manufacturer’s Name
or Trademark
Year of Manufacture
f) Hose
in service shall be requalified periodically in accordance with requirements
specified in CGA P-7.
g) Hoses
used for transferring material (both liquid and vapor) to and from nurse tanks
shall be restricted to a 30 feet maximum length and shall be secured when not
in use to prevent undue damage to hose.