8 Ill. Adm. Code 257.80
Structural Requirements
Section 257
Section 257.80 Structural
Requirements
In addition to the requirements
included in 8 Ill. Adm. Code 255 for agrichemical facilities, 8 Ill. Adm. Code
256 for lawncare facilities, and Section 257.70 of this Part for central
distribution facilities, the following shall be required of facilities affected
by this Part:
a) The use of underground structures, pits, or piping for the
storage or transport of product, rinsates, wash water, or recycled liquid at
any facility affected by this Part is prohibited. This prohibition shall not
include sumps or wet wells which are used for the transfer of product,
rinsates, wash water, or recycled liquid provided these structures maintain a
detention time of seventy-two (72) hours or less.
b) All pesticide-related operational containment structures
located at an agrichemical facility subject to 8 Ill. Adm. Code 255 shall be
covered/protected from precipitation. This requirement shall include
operational areas associated with the impregnation of dry fertilizer with
pesticides.
c) All bulk pesticide storage tanks installed at agrichemical
facilities subject to the provisions of 8 Ill. Adm. Code 255 shall be
prohibited from being constructed of poly-materials unless a distance not less
than one-half the total tank height is maintained between the perimeter of the
tank wall and the interior wall surface of the secondary containment structure.
d) All filled mini-bulks and packaged goods shall be warehoused
in a designated secondary containment structure on a surface with a hydraulic
conductivity not to exceed 1 X 10
-6
cm/sec constructed and 1 X 10
-5
cm/sec maintained. The surface shall be constructed of an impervious material
compatible with the products being stored and capable of being properly
decontaminated. The designated secondary containment structure shall include a
minimum of a four (4) -inch curb or other flow-diverting structure or system to
allow for the interception and retention of spilled materials within the
secondary containment area. The minimum four (4) -inch curb or other
flow-diverting structure or system shall completely surround the designated
secondary containment structure. There shall not be penetrations in the floor
and all existing floor drains shall be sealed with a non-shrink grout. This
requirement shall only apply to facilities which store at least 300 gallons or
300 pounds of pesticides; or 1,500 gallons of fertilizers in mini-bulks and
packaged goods at any one time.
e) All transfer of agrichemicals between containers, including
loading, unloading, repackaging and mixing, and equipment cleaning performed at
an agrichemical facility subject to the provisions of 8 Ill. Adm. Code 255
shall be conducted within a containment system designed to intercept, retain,
and recover operational and accidental spillage, leakage, wash water, and
agrichemical residues. Construction materials of containment structures shall
be compatible with the products handled and maintained in a condition to retain
recovered material until it is used or properly disposed of. A containment
system for such transfer piping during either a loading or unloading operation
shall consist of one of the following:
1) concentric piping, catch trays, trenches, raceways, etc., or
2) annual pressure testing and visual inspection of the piping if
constructed of stainless steel, or
3) annual pressure testing and visual inspection of the piping if
constructed of materials other than stainless steel and the piping is not
allowed to stand full of material during periods of non-operation.