Cite as Ind. Admin. Code tit. 410, r. 7-21-41
Sec. 41. Each facility shall be equipped with effective plumbing and sewage facilities and adequate accommodations, including, but not
limited to, the following:
(1) The water supply shall be sufficient for the operations intended and shall be derived from an approved source. Drinking water and
water used for food processing operations shall meet bacteriological and chemical quality standards specified in 327 IAC 8-2. Running
water at a suitable temperature and under pressure as needed shall be provided in all areas where required for the processing of food, for the cleaning
of equipment, utensils, and food-packaging materials, or for employee sanitary facilities.
(2) If a food processing plant obtains water from a water system not subject to 327 IAC 8-2 for its operations, the operator
shall sample the water at least annually for bacterial analysis by a certified laboratory, maintain records of analyses of sample results for three (3)
years, and provide such records to the department upon request.
(3) A plumbing system shall be of sufficient size and shall be designed, constructed, installed, and maintained according to the
applicable Indiana plumbing code, 675 IAC 16-1.3, to do the following:
(A) Carry sufficient quantities of water to required locations throughout the facility.
(B) Properly convey sewage and liquid disposable waste from the facility.
(C) Avoid constituting a source of contamination to food, water supplies, equipment, and utensils or creating an unsanitary
condition.
(D) Provide sufficient floor drainage in all areas where floors are subject to flooding-type cleaning or where normal operations release or
discharge water or other liquid waste on the floor.
(E) Prevent backflow or backsiphonage from, or cross-connection between, piping systems that discharge wastewater or sewage and piping
systems that carry water for food or food manufacturing. This shall be accomplished by the following:
(i) Installing a backflow or backsiphonage prevention device on a water supply system which meets the standards in 675 IAC 16-1.3 for construction, installation, maintenance, inspection, and testing for that specific application and type of approved device.
(ii) Using an air gap, if necessary, between the water supply inlet and the flood level rim of the plumbing fixture, equipment, or nonfood
equipment. It shall be at least twice the diameter of the water supply inlet and may not be less than one (1) inch.
It shall be a minimum of two (2) pipe diameters of the pipe or six (6) inches, whichever is the lesser.
(4) Sewage disposal shall be conveyed into an approved sanitary sewerage system or other system, including the use of sewage
transport vehicles, pumps, hoses, and connections that are constructed, maintained, and operated according to law.