675 IAC 15-2-104 Polarization
Cite as Ind. Admin. Code tit. 675, r. 15-2-104
Sec. 104. (a) The identified (white) conductor shall be employed for grounded circuit conductors only and shall be connected to the
identified (white) terminal or lead on receptacle outlets and fixtures. It shall be the unswitched wire in switched circuits, except that a cable
containing an identified conductor (white) shall be permitted for single-pole three (3) way or four (4) way switch loops where the connections are
made so that the unidentified conductor is the return conductor from the switch to the outlet. Painting of the terminal end of the wire shall not be
required.
(b) If the identified (white) conductor of a cable is used for other than grounded conductors or for other than switch loops as explained
above (for a two hundred thirty (230) volt circuit, for example), the conductor shall be finished in a color other than white at each outlet where the
conductors are visible and accessible.
(c) Green-colored wires or green with yellow stripes shall be used for grounding conductors only.