675 IAC 15-2-63
675 IAC 15-2-63 Anti-siphon trap vent
Cite as Ind. Admin. Code tit. 675, r. 15-2-63
Sec. 63. (a) Anti-Siphon Trap Devices. Where an anti-siphon trap vent device is used as a secondary vent, it shall be installed in accordance
with the conditions of its listing and shall be accessible. The lowest point of the valve seal when in the normally closed position shall not be less
than six inches (6") above the flood level of the fixture. The toilet shall be vented in accordance with 675 IAC 15-2-62. Only anti-siphon
trap vent devices which have been approved shall be installed.
(b) Not more than two (2) fixtures individually protected by anti-siphon trap vent devices shall be drained by a common one and one-half
inch (1 1/2") drain.
(c) Three (3) or more fixtures individually protected by anti-siphon trap vent devices shall be drained by a common two inch (2") drain.