675 IAC 30-8-11
675 IAC 30-8-11 Steam gauges; shutoff valves; nipple and globe valves
Cite as Ind. Admin. Code tit. 675, r. 30-8-11
Sec. 11. (a) Each steam boiler shall have a steam gauge, with a dial range not less than one and one-half (11/2) times the MAWP, that is
connected to the steam space or to the steam connection to the water column. The steam gauge shall be connected to a siphon or equivalent device
of sufficient capacity to keep the gauge tube filled with water, and so arranged that the gauge cannot be shut off from the boiler except by a cock
placed near the gauge and provided with a tee or lever handle arranged to be parallel to the pipe in which it is located when the cock is
open.
(b) When a steam gauge connection longer than eight (8) feet becomes necessary, a shut off valve may be used near the boiler provided
the valve is of the outside screw and yoke type and is locked open. The line shall be ample size with provisions for free blowing.
(c) Each boiler shall be provided with a one-fourth (1/4) inch nipple and globe valve connected to the steam space for the exclusive purpose
of attaching a test gauge when the boiler is in service so that the accuracy of the boiler steam gauge may be ascertained.