675 IAC 30-8-12
675 IAC 30-8-12 Stop valves; drainage
Cite as Ind. Admin. Code tit. 675, r. 30-8-12
Sec. 12. (a) Each steam outlet from a boiler (except safety valve connections) shall be fitted with a stop valve located as close as practicable
to the boiler.
(b) When a stop valve is so located that water can accumulate, ample drains shall be provided. The drainage shall not be discharged on
the top of the boiler or its setting.
(c) When boilers provided with manholes are connected to a common steam main, the steam connection from each boiler shall be fitted
with two (2) stop valves having an ample free blow drain between them. The discharge of this drain shall be visible to the operator while
manipulating the valves and shall be piped clear of the boiler setting. The stop valves shall consist preferably of one (1) automatic nonreturn valve
(set next to the boiler) and a second valve of the outside-screw-and-yoke type.