326 IAC 11-7-7
326 IAC 11-7-7 Compliance and performance testing
Cite as Ind. Admin. Code tit. 326, r. 11-7-7
Sec. 7. (a) The owner or operator of a designated facility shall comply with the compliance and performance testing methods and
procedures specified in 40 CFR 60, Subpart Eb, Section 60.58b*, except as provided in subsections (b) through (c). All tests shall meet the
requirements of 326 IAC 3-6.
(b) If all of the dioxin/furan compliance tests for all designated facilities over a two (2) year period indicate that the dioxin/furan emissions
are less than or equal to fifteen (15) nanograms per dry standard cubic meter corrected to seven percent (7%) oxygen, the owner or operator of the
plant may elect to conduct an annual dioxin/furan performance test for one (1) designated facility (unit) per year at the plant. At a minimum, a
performance test for dioxin/furan emissions shall be conducted annually (no more than twelve (12) months following the previous performance test)
for one (1) designated facility at the plant. Each year a different designated facility shall be tested. The designated facilities at the plant shall be tested
in sequence, such as Unit 1 the first year, followed by Unit 2 the next year.
(c) If an annual performance test indicates an emission level for dioxin/furan greater than fifteen (15) nanograms per dry standard cubic
meter corrected to seven percent (7%) oxygen, then performance tests shall be conducted annually on all designated facilities at the plant until all
annual performance tests for all designated facilities at the plant over a two (2) year period indicate a dioxin and furan emission level less than or
equal to fifteen (15) nanograms per dry standard cubic meter corrected to seven percent (7%) oxygen.
(d) The owner or operator of a designated facility who elects to follow the performance testing schedule specified in subsection (b) shall
follow the procedures specified in 40 CFR 60, Subpart Eb, Section 60.59b(g)(4)*, for reporting the election of this schedule to the
department.
*These documents are incorporated by reference. Copies may be obtained from the Government Printing Office, 732 North Capitol Street
NW, Washington, D.C. 20401 or are available for review and copying at the Indiana Department of Environmental Management, Office of Air
Quality, Indiana Government Center-North, Tenth Floor, 100 North Senate Avenue, Indianapolis, Indiana 46204.