327 IAC 8-3.2-13
327 IAC 8-3.2-13 Use of dead-end mains
Cite as Ind. Admin. Code tit. 327, r. 8-3.2-13
Sec. 13. (a) All dead-end mains shall end with a valve and one (1) additional length of pipe beyond the valve that is properly plugged and
capped.
(b) All dead-end main end points shall have flushing devices attached to the valve specified in subsection (a) that is sized to provide at
least two and one-half (2.5) feet per second and a maximum of five (5) feet per second in the dead-end main during flushing. No flushing device
may be connected directly to a sewer. A flushing device shall be selected in accordance with the following:
(1) The flushing device shall be a fire hydrant, flushing hydrant, or blow-off assembly if the diameter of the water main pipe is at least
six (6) inches in diameter.
(2) The flushing device shall be a flushing hydrant or blow-off assembly if the diameter of the water main pipe is less than six (6)
inches in diameter.