LAC 43:XIII.1313

LAC 43:XIII.1313. Miter Joints [49 CFR 192.233]

Last amended: 2004Year: 2026Length: 140 wordsOfficial source

Cite as La. Admin. Code tit. 43, pt. XIII, § 1313

A. A miter joint on steel pipe to be operated at a pressure that produces a hoop stress of 30 percent or more of SYMS may not deflect the pipe more than 3°. [49 CFR 192.233(a)] B. A miter joint on steel pipe to be operated at a pressure that produces a hoop stress of less than 30 percent, but more than 10 percent of SMYS may not deflect the pipe more than 12 1/2° and must be a distance equal to one pipe diameter or more away from any other miter joint, as measured from the crotch of each joint. [49 CFR 192.233(b)] C. A miter joint on steel pipe to be operated at a pressure that produces a hoop stress of 10 percent or less of SMYS may not deflect the pipe more than 90°. [49 CFR 192.233(c)]
LAC 43:XIII.1313: LAC 43:XIII.1313. Miter Joints [49 CFR 192.233] | Justis AI