310 CMR 15.240
Soil Absorption Systems
(1) On-site subsurface sewage disposal systems shall be located in an area where there is at least
a four foot depth of naturally occurring pervious soil below the entire area of the soil absorption
area and reserve area unless a variance is issued in accordance with the provisions of 310 CMR
15.415(2). The four foot stratum must be free of impervious and unsuitable materials.
(2) Effluent from any component of an on-site sewage disposal system shall not be disposed
of by direct discharge to any waters of the Commonwealth, unless in compliance with a permit
issued pursuant to 314 CMR 3.00 (surface water permitting) or 314 CMR 5.00 (groundwater
permitting).
(3) Soil absorption systems shall be designed as an integral part of the system. Septic tank
effluent is to be distributed throughout the soil absorption system by means of effluent
distribution lines so that the effluent can migrate through the underlying soil column under
unsaturated flow conditions. All soil absorption systems shall achieve the following objectives
of the soil treatment process:
(a) maximum stabilization of organic wastes in the effluent;
(b) removal of pathogenic organisms, nutrients, and particulates;
(c) recharge of the ground-water table with adequately treated effluent with minimal
attendant pollution of the groundwater; and
(d) disposal of the effluent without discharge to the ground surface or the creation of any
nuisance.
(4) The minimum area for the design of a soil absorption system shall be determined by the
results of the site evaluation set forth in 310 CMR 15.100 through 15.107 and in accordance with
the appropriate long-term acceptance rate criteria specified in 310 CMR 15.242 (effluent loading
rates). Area requirements increase by 50% when garbage grinders are installed and the system
shall be upgraded to meet such requirements prior to the installation of a garbage grinder.
(5) All soil absorption systems designed to serve single family dwellings, including but not
limited to single family condominiums and cooperatives, shall be designed to serve a minimum
of three bedrooms, unless a deed restriction limiting use to two bedrooms is granted to the local
Approving Authority.
(6) Absorption trenches should be used whenever possible.
(7) No driveway, parking or turning area or other impervious area shall be located above a soil
absorption system, except where restrictions on the use of the land make it unavoidable. In such
cases, the soil absorption system shall be vented to the atmosphere in accordance with 310 CMR
15.241.
(8) The bottom of each soil absorption system shall be excavated to a level grade. If the removal
of stones or boulders is required, creating localized depressions, filling to grade with the
excavated naturally occurring pervious soil or material in compliance with 310 CMR 15.255 is
acceptable.
(9) The soil placed as backfill over the soil absorption system shall be a minimum of nine
inches, excluding topsoil, placed in lifts and sufficiently compacted to prevent depressions due
to settling which may intercept or collect surface water runoff above the system. Backfill must
be clean and free of stones and boulders greater than six inches in size. Tailings, clay or similar
materials are prohibited.
(10) Final cover above the system shall be stabilized and graded to reduce infiltration of surface
water and minimize erosion. Finish grade shall have a minimum slope of 0.02 feet per foot.
(11) Surface drainage shall be directed away from the soil absorption system.
(12) For systems with a design flow of 2,000 gpd or greater, the separation distance to the high
groundwater elevation required by 310 CMR 15.212 shall be determined by adding the effect of
groundwater mounding to the high groundwater elevation as determined pursuant to 310 CMR
15.103(3).
(13) All soil absorption systems shall have a minimum of one inspection port consisting of a
perforated four inch pipe placed vertically down into the stone to the naturally occurring soil or
sand fill below the stone. The pipe shall be capped with a screw type cap and accessible to
within three inches of finish grade.