105 CMR 150.020
Skilled Nursing Care Facility (Level II) and Supportive Nursing Care Facility
(Level III) and 150.310: Required Supporting Elements - Nursing Care Units.
(3) A DSCU shall meet the requirements listed in 105 CMR 150.029(B) through (K) in
addition to the requirements set forth in 105 CMR 150.017.
(B) Access. The design of the DSCU shall not require visitors or staff to pass through the unit
to reach other areas of the facility.
(C) Outdoor Recreation Space.
A DSCU shall have secured outdoor space and walkways allowing residents to
ambulate, with or without assistive devices such as wheelchairs or walkers, but that prevent
undetected egress.
(2) Such outdoor space and walkways shall be wheelchair accessible.
Residents shall have access to the secured outdoor space and walkways during
reasonable times with supervision appropriate to each resident.
Outdoor recreation space shall have fencing or barriers that prevent injury and
elopement.
(D) Lighting.
(1) The DSCU shall provide adequate and evenly distributed lighting that minimizes glare
and shadows and is designed to meet the specific needs of the residents.
(2) Artificial lighting shall meet the lighting requirements of the Guidelines for Design and
Construction of Residential Health, Care and Support Facilities from the Facility Guidelines
Institute.
(E) Finishes.
(1) Finishes shall include high visual contrasts between floors and walls and between
doorways and walls in resident use areas. Except for fire exits, door and access ways not in
resident use areas may be designed to minimize contrast to obscure or conceal areas the
residents should not enter.
(2) Floors, walls and ceilings shall be non-reflective to minimize glare.
(3) Flooring shall not include contrasted visual patterns.
(F) Resident Centered Environment. The DSCU shall promote a resident centered environment
that includes the following:
(1) Freedom of movement within the DSCU for the residents including to common areas
and to their personal spaces, including bedrooms, at all times;
(2) Assistive equipment that maximizes the independence of individual residents;
(3) Comfortable seating in the common use areas;
(4) Bedroom decoration and furnishings that include residents’ personal items based on the
resident’s needs, preferences and appropriateness;
(5) In addition to the requirement of 105 CMR 150.015(F)(3), individual identification of
each resident’s bedroom based on the resident’s cognitive level to assist residents in locating
their bedrooms, and to permit them to differentiate their bedroom from the bedrooms of other
residents; and
(6) Corridors and passageways through common-use areas kept free of objects that may
cause falls, or obstruct passage by physically impaired individuals.
(G) Noise Control.
(1) The DSCU shall have acoustical ceilings in corridors, dining areas and activity areas to
reduce noise levels.
No overhead paging system shall be used in the DSCU except in the case of an
emergency.
The sound signal for the nurses call system shall be adjustable so as to minimize
disruption of residents and resident activities.
(H) Egress Control.
(1) The facility shall develop policies and procedures to ensure the safety of residents who
may wander. The procedures shall include actions to be taken to prevent elopement and
actions in case a resident elopes.
(2) Locking devices shall be used on exit doors, as approved by the local building inspector
and fire department having jurisdiction over the facility. The locking devices shall be
electronic and release when the following occurs:
(a) activation of the fire alarm or sprinkler system;
(b) loss of electrical power; or
(c) use of a keypad located at each locked door for routine staff access. The electronic
locking devices shall be connected to the emergency power circuits.
(3) If the DSCU uses keypads to lock and unlock exits, then directions for their operation
shall be posted on the outside of the door to allow individuals access to the unit. However,
if the DSCU is the entire nursing home, then directions for the operation of the locks need
not be posted on the outside of the door. The DSCUs shall not have entrance and exit doors
that are closed with non-electronic keyed locks, nor shall a door with a keyed lock be placed
between a resident and the exit.
(I) Safety.
(1) Windows shall be operable and equipped with secure locks under the control of the
DSCU staff.
(2) In conjunction with locked windows, the DSCU shall be equipped with a cooling system
capable of maintaining a maximum temperature of 75EF throughout resident areas at all
times at summer design temperatures. Temperatures must be maintained at a level that
ensures the comfort and health of residents.
(J) Common Space. A multipurpose room or rooms for dining, group and individual activities,
and family visits comply with the following licensure requirements for common space shall be
included in the DSCU. The floor areas of this multipurpose room or rooms shall accommodate
the licensure requirements of at least ten square feet per bed for dining per 105 CMR 150.570:
Central Dining, at least eight square feet per bed for group activities per 105 CMR 150.510:
General and Special Activity Areas and at least nine square feet per bed for day room per
105 CMR 150.360: Activity Area — Nursing Care Units, for a total of at least 27-square feet per
bed.
(K)
Implementation. A facility may request additional time to implement physical plant
modifications necessary to meet the requirements of 105 CMR 150.029 pursuant to Department
guidelines.