248 CMR 7.03
Installation of Burners and Controls
(1) Main Burners.
(a) Each burner assembly and its component parts shall be installed according to the
manufacturer's instructions and shall be properly and firmly secured in place to maintain
correct alignment in normal use.
(b) The burner assembly shall be installed so that sufficient accessibility is afforded for
cleaning, inspection, repair, and replacement of all burners, controls and safety devices.
(c) Burner assembly parts, when adjustable, shall be provided with suitable locking devices
to prevent accidental shifting.
(d) Provision shall be made to permit ready observation of each pilot and main burner flame
during adjustment and under operating conditions.
(e) A burner assembly, when adjusted according to the manufacturer's instruction, shall
maintain satisfactory operating characteristics as specified in 248 CMR 7.04(5) at all firing
rates called for by input and air-gas ratio controls applied to the installation.
(2) Control Application.
(a) Each control shall be supported in such a manner that it and its sensing element will
remain in proper position. It shall be possible to determine by observation or test that each
control is in its proper location and capable of functioning as intended.
(b) Nothing shall be provided for the purpose of permitting any safety control to be rendered
ineffective or allowing firing of the burner assembly without the protection of all of the
specified safety controls except as permitted by 248 CMR 7.03(2)(c).
(c) A low-water cutoff may be bypassed for blow-down purposes only. Such a bypass shall
be of a type which must be manually held in the bypass portion and which is self-restoring
when released.
(d) A burner assembly not equipped to provide safe automatic restarting shall be arranged
to require manual restart after any control functions to cause the fuel supply to be shut off
and the following restoration of an interrupted power supply.
(e) The safety-control circuit shall be two-wire, one side grounded, having a nominal
voltage of 150 volts or less. The circuit shall be connected to a branch circuit that can be
protected against over current at not more than the value appropriate for the rating of the
electrical components included in the circuit.
(f) A safety control or protective device switch shall interrupt the ungrounded conductor(s).
(g) Safety controls shall not depend on electricity to attain the off position.
(3) Control of Combustion Air.
(a) An air shutter shall be capable of being readily adjusted to any desired setting and
securely locked to prevent accidental change in setting.
(b)
The air inlet(s) shall supply an adequate amount of air for combustion under the
specified draft conditions and at the maximum firing rate of the burner assembly as installed.
All air required for combustion shall be introduced in a manner so as to provide thorough
mixing of the gas and air. If a burner is intended for installation with an air or wind box(es),
it shall be supplied by the burner manufacturer or be built in accordance with the burner
manufacturer's instructions.
(c) Linkage for controlling air and gas input rates shall be designed to reliably maintain the
correct gas-air ratio and to resist accidental damage and disengagement.
(d) Equipment having forced or induced draft fans or both, shall be provided with means
to automatically continue safe combustion or to shut off the gas supply upon failure of the
equipment supplying the air.
(e) If air under pressure is mixed with the gas supply in a mixer, effective means shall be
provided to prevent air from passing back into the gas line or gas into the air supply. The gas
and air supply shall be controlled to prevent gas from entering burners until the air supply
is available and, in the event of air failure, to shut off the gas supply.
(4) Primary Safety Control (Flame Safeguard).
(a) Unless a flame safeguard control is provided by the manufacturer, each burner assembly
shall be provided with a non-recycling primary safety control that will de-energize the main
gas safety shutoff valve(s) upon loss of flame at point of supervision.
(b) Safety control timings shall not exceed the values given in 248 CMR 7.03: Table 1.
(c) Gas to pilots shall be automatically shut off if the pilot is not proved, and safety
shutdown established.
(d) Pilot supervision by the primary safety control shall be only at the point where the pilot
flame will effectively ignite the gas at the main burner or burner group with the pilot burning
at any flame that will actuate the safety control.
(e) Supervision of the main burner flame only shall begin at the end of the main burner
flame-establishing period for:
1. Power burners having a firing rate per combustion chamber of 2,500,000 Btu per
hour and over.
TABLE 1
Maximum Safety Control Timings
Maximum Firing Rate Per Combustion
Chamber in Million Btu Per Hour
2.5 or less
Over 2.5 to 12.5
Over 12.5
Pilot Flame Establishing Period
15 Seconds
10 Seconds
10 Seconds
Main Burner Flame Establishing
Period (If Required)
15 Seconds *
10 Seconds
10 Seconds *
Flame Failure Response Time
4 seconds
4 Seconds
4 Seconds
Valve Closing Time
5 Seconds
1 Second
1 Second
*
Main burner flame-establishing period may be 30 seconds for burner other than power burners equipped
with a safety shutoff valve having a full opening time of not less than 25 seconds.
2. All types of burners with modulating or high-low firing rate per combustion chamber
of 2,500,000 Btu per hour and over.
3. All types of burners with an interrupted pilot(s), and
4. Atmospheric type burners having a firing rate per combustion chamber of 5,000,000
Btu per hour and over. If the main burner flame is not proved, safety shutdown shall be
established.
(f) A burner assembly shall be equipped so that no gas can flow to the main burner on
burner group operating as a unit unless the pilot is proved.
(g) If two or more burner assemblies are installed in a single piece of equipment, the
primary safety control of each burner assembly shall operate independently of the other, or
equivalent safety features shall be provided so that in no case can any one burner operate
unsafely.
(5) Limit Controls.
(a) Limit Control.
1. A limit control shall be provided to prevent excessive steam pressure in a steam
boiler or excessive pressure or temperature in a hot water boiler.
2. Each steam and hot water boiler shall be equipped with a control which will prevent
firing of the boiler in the event of insufficient water in the boiler.
3. The limit control shall be in addition to operating controls. Manual restart shall be
required after a pressure or temperature limit control functions.
(b) A limit control which functions by opening a switch shall directly open the electrical
circuit to the safety shutoff valve(s).
(6) Combustion (Input) Control Systems.
(a) The combustion (input) control system shall maintain predetermined air-fuel mixtures
within the limits required by the burner for stable combustion throughout the entire operating
range of the burner and during changes in the firing rate.
(b) To accomplish changes in the firing rate, the fuel and air supplies shall be maintained
at a pre-determined optimum air-fuel ratio, either manually or automatically.
(c) Burners having a firing rate per combustion chamber of 1,000,000 Btu per hour and over
shall be equipped with a proven low-fire start.
(d) Burners having a firing rate per combustion chamber of 2,500,000 Btu per hour and over
shall be provided with combustion control.
(7) Pilots.
(a) Main burners shall be equipped with a supervised pilot adequate to provide safe main
burner ignition under all conditions of operation. Multiple burner heads operated as a single
burner unit shall use a sufficient number of supervised pilots to accomplish safe ignition.
(b) A pilot burner not automatically lighted shall be located so that it can be safely lighted
manually.
(c) Gas supply pressure to the pilot or group of pilots:
1. The gas supply pressure to the pilot or group of pilots shall be regulated.
2. The regulator(s) shall be listed; and vented in accordance with 248 CMR 7.03(11)(c),
unless constructed or equipped to limit the escape of gas from the vent opening in the
event of diaphragm failure to not more that 2.5 cubic feet per hour.
3. The pilot supply line shall be connected upstream of all main burner valves and the
main gas pressure regulator.
(d) Primary air openings and orifices shall be easily accessible for servicing.
(e) An electric ignition system shall ignite only a pilot.
(f) If means for ignition is cut off at the termination of either the main burner flame-
establishing period, the ignition shall remain off for the duration of that firing cycle and for
the specified purge period.
(g) A pilot burner, electric igniter, and pilot flame sensing device shall be supported in such
a manner that their position relative to each other and to the main burner port(s) will remain
fixed.
(8) Gas Valve Pressure Ratings.
(a) Gas valves shall be capable of withstanding without damage a pressure of not less than
10% above the relieving pressure of the nearest upstream relief device.
(b) In case no relief device is provided, the gas valves shall be capable of withstanding
without damage a pressure of not less than the maximum inlet pressure of the nearest
upstream gas pressure regulator or the maximum setting of the over-pressure protection
device.
MANUAL MAIN PILOT
SHUTOFF VALVE
248 CMR 7.04: (9Xb)
MANUAL SHUTOFF VALVE
248 CMR 7.04: (9Xf)
MANUAL MAIN BURNER TEST VALVE
248 CMR 7.04: (9Xd)
MANUAL MAIN BURNER SHUTOFF VALVE
248 CMR 7.04: (9Xd)
QonIONAL BOIL§!) }
>--"- ➔--- ➔ -- ➔
(9) Manually Operated Gas Shutoff Valves. (See 248 CMR 7.03: Figures 1 and 2.)
(a) A manually operated main burner shutoff valve shall be installed in the line supplying
all main burners of each piece of equipment and upstream of all other main burner control
valves.
(b) A manually operated main pilot shutoff valve shall be located in the gas supply line to
the pilot burner.
(c) Manually operated main shutoff and pilot shutoff valves in sizes larger than two inches
or for pressures greater than ½ psig shall be of the lubricated plug or ball type with stops.
Manually operated valves shall have the handle securely attached parallel to the gas flow in
the open position, shall be readily accessible, and shall clearly indicate the "on" and "off"
positions.
(d) A manually operated main burner test valve (checking gas cock) shall be provided
downstream from the safety shutoff valve for each main burner. On manually lighted
burners, the valves shall be interlocked with the safety control circuit and arranged so that
the main burner safety shutoff valves must be opened against their associated closed test
valves.
(e) In multiple burner installations a manual valve shall be provided for each main and each
pilot burner except those utilizing a single zero governor inspirator mixer for several burners
in which case this valve shall be located at a point immediately upstream of the zero
governor.
(f) Provisions shall be made so that the gas supply to equipment may be shut off from a
location outside the room where said equipment is located.
FIGURE 1
Illustration of Manual Valving Arrangement for a Multiple Burner, Single Boiler Arrangement
PILOT YALYE(S)
248 CMR 7.04: (9Xe)
MANUAL MAIN PILOT
SHUTOFF VALVE
248 CMR 7.04: (')f.lt)
MAIN SHUTOFF VALVE
248 CMR7.14: (9)(f)
MANUAL MAIN BURNER TEST VALVE
248 [MR 7.04: (9)(d)and.
248 (MR 7 .04: (!IXe)
MANUAL MAIN BURNER SHUTOFF VALVE
248 CMR 7.041 C!'Xa)
FIGURE 2
Illustration of Manual Valving Arrangement for a Multiple Burner, Single Boiler Arrangement
MANUAL
(10) Control and Safety Shutoff Valves. (See 248 CMR 7.03: Figure 3.)
(a) An automatic input control valve may be in combination with a safety shutoff valve.
(b) A bypass to provide for minimum flame may be installed around a valve to control
input only. A bypass shall not be installed around a safety shutoff valve or a combustion
input control and safety shutoff valve.
(c) Safety Valves:
1. Each main burner supply line and each pilot supply line shall be equipped with a
safety shutoff valve(s) which will close independent of external force.
2. The safety shutoff valve(s) shall close with sufficient force to provide tight shutoff
under normal operating conditions and when closed by the safety control system or by
an emergency device.
3. If the maximum firing rate per combustion chamber exceeds 1,000,000 BTU/hour,
the main burner supply line shall be equipped as indicated in 248 CMR 7.03(10)(c)3.a.
and b.:
Line
A = Shutoff Valve Within SiK Feet
of Entrance to Gas Train
B = Union
C = Start of Gas Train
Burner Pressure
Test Port
D ::Pilot Line to Outside Unless F.quipped
with Limiting Device of 2.5 cu. ft.lhr
E = Vent to Outside Per Table 2
E
Safety Shutoff
Valve
I
Pressure Regulator
[)J
To Main Burner
Burner Pressure
Test Port
Safety Shutoff
Valve
a.
Two safety shutoff valves, in series, or one safety shutoff valve of the type
incorporating a valve seal overtravel interlock, when the maximum firing rate per
combustion chamber exceeds 1,000,000 BTU/hour but less than 5,000,000
BTU/hour.
b. Two safety shutoff valves, in series, one of which is of the type incorporating a
valve seal overtravel interlock when the maximum firing rate per combustion
chamber exceeds 5,000,000 BTU/hour.
The Board may prescribe two safety shutoff valves in series, for combustion
chambers with inputs less than 1,000,000 BTU/hour, in buildings of public assembly.
(d) Safety shutoff valves shall be suitable for the application and shall have a shutoff time
not to exceed that specified in 248 CMR 7.03: Table 1. They shall be constructed so that
they cannot be restrained or blocked in the open position. Such valves shall close upon being
de-energized regardless of the positions of damper-operating levers or reset handles.
(e) An electrically operated safety shutoff valve shall not depend on electricity to shut off
the gas supply.
(f)
A pressure-operated safety shutoff valve shall close upon failure of its operating
pressure.
(g) Permanent and ready means for making easy, accurate, periodic tightness tests of the
main burner gas safety shutoff valves shall be provided in the piping.
FIGURE 3A.
Illustration of Gas Train 248 CMR 3.00 through 7.00 requirements 400,000 to Less Than 1,000,000
BTU/hour Input
Pilot
Pressure
Switch
Safety Shutoff Valve
with Valve Sul
Overtravel Interlock
Safety Shutoff Valve
Pilot Line
Manual Shutoff
Valve
A = Shutoff Valve Within Six Feet
of Entrance to Gas Train
B = Union
[ = Start of Gas Train
D = IDot V«i:tto Ou:tsitt Uriltfs F/tlJil,pEd. ,,.nti.
limmn{ Ilewe o1 2 5 Cll.ftJlir
E = Vent to Outside Per Table 2
F = Combination High and Low Pressure
Switch Allowed at Low Pressure
Switch Location
Vent to
Outside
Pressure
Regulator
Safety Shutoff
Valve
To Main
Burner
Burner Pressure
Test Port
FIGURE 3B.
Illustration of Gas Train 248 CMR 3.00 through 7.00 1,000,000 to Less Than 2,500,000 BTU/hour Input
Low
Manual Shutoff Valve
Manual Shutoff Valve
Lo,~ Pressure
Switch
Manual Shutoff Valve
Safety Shutoff Valve
Safety Shutoff Valve
with Valve Seal
Overtravel Interlock
High Pressure
Switch
~
Safety Shutoff
Valve
Manual Shutoff Valve
FIGURE 3C.
Illustration of Gas Train 248 CMR 3.00 through 7.00 requirements for 2,500,000 to less than 5,000,000
BTU/hour Input
A = Shutoff Valve Within Six Feet
of Entrance to Gas Train
B = Union
C = Start of Gas Train
D = Pilot Vent to Outside Unless
Equipped with Limiting Device
of 2.5 cu. ft./hr
E =
Vent to Outside per Table 2
F =
Combination High and Low
Pressure Switch Allowed at
Low Pressure Switch Location
Manual Shutoff Yalve
Low Pressure
Switch
Manual Shutoff Valve
Safety Shutoff Valve
,
R - -- -- -__ /
""L-w-it_h_v_a_l_v_e_s_e_a_•_
I"'--_.., ____ -.
~
Omomollnoo,lo,,
High Pressure
Safety Shutoff Valve
Switch
___ A..._ __
I
Manual Shutoff V alvel
Safety Shutoff
Valve
I
FIGURE 3D
Illustration of Gas Train 248 CMR 3.00 through 7.00 requirements for 5,000,000 to less than 12,500,000
BTU/hour Input
A =
Shutoff Valve Within Six Feet of
Entrance to Gas Train
B =
Union
C =
Start of Gas Train
D =
Pilot
Vent
to
Outside Unless
Equipped with Limiting Device of
2.5 cu. ft./hr
E =
Vent to Outside per Table 2
F =
Combination
High
and Low
Pressure Switch Allowed at Low
Pressure Switch Location
G =
May be Part of SSOV
(11) Main Gas Pressure Regulators and Gas Pressure Interlocks.
(a) Each burner assembly shall be equipped with a listed main gas pressure regulator that
will regulate within plus or minus 10% of the operating pressure at all firing rates. (See
248 CMR 7.03: Figure 3 for location).
(b) Spring or weight-loaded regulators shall have springs covered by a suitable housing.
Under no circumstances shall a weight and lever type of regulator be used.
(c) Main Gas Pressure Regulators:
1. Except where zero governors are used in connection with air-gas mixers, all main gas
pressure regulators shall be independently vented to a safe outdoor location.
2. Vent lines from main gas pressure regulators shall not be connected into a common
line with the bleed line from gas operated diaphragm valves or from pressure relief
valves.
3.
Vent lines shall be steel, wrought iron pipe or corrugated stainless steel tubing
(CSST) with Product-approved devices provided at termination points to prevent
stoppage of the lines by foreign material, water or insects and, shall extend no less than
18 inches above the roof surface.
4. Vent lines shall be sized as specified in 248 CMR 7.03: Table 2.
5. Vent lines shall be supported in accordance with 248 CMR 1.00 through 10.00.
6. Vent lines shall be run to the outside using the shortest practical route and shall not
be trapped or installed in a manner that restricts air-flow.
7. Vent lines that penetrate roofs and sidewalls shall be run through metallic sleeves that
are sealed from the weather and insects.
8. CSST vent lines that penetrate roofs shall transition to steel pipe no less than one foot
inside the building.
9. Vent lines that terminate outside a building shall be located no less than four-feet
away from any building opening or air intake and ten feet away from forced air intakes.
Outside
(d) Pressure Switches.
1. If the maximum firing rate per combustion chamber is 1,000,000 BTU/hour or over,
gas pressure supervision shall be provided by listed pressure switches, or listed
combination high-low switch, interlocked to accomplish a non-recycling safety shutdown
in the event of either high or low gas pressure.
2. Pressure setting shall be adjusted by the installer in accordance with the burner or
equipment manufacturer's instructions.
3. Pressure switches that require venting to the outside atmosphere shall be vented in
accordance with 248 CMR 7.03(11)(c). Pressure switches only may be manifolded.
(e) Accessible IPS plugged pressure tappings or connections shall be provided; one located
upstream of the main gas pressure regulator and another located near the burner head to
permit accurate measurement of gas pressure. (See 248 CMR 7.03: Figure 3.)
TABLE 2
Minimum Pipe Size/CSST for Venting
Gas Train Components in 248 CMR 7.04 Figures 3a, 3b, 3c, and 3d.
Gas Train Components
Maximum lengths of iron pipe or corrugated stainless steel
tubing (CSST) from components to outside the building
0 - 40 feet
0 - 100 feet
0 - 200 Feet
Main Gas Pressure Regulator
- Steel Pipe Size
- CSST Size (Low Pressure Gas only)
¾ inch IPS
30/31 EHD
1 inch IPS
37 EHD
1¼ inch IPS
46/48 EHD
High & Low Gas Pressure Switches
When Manifolded
- Steel Pipe Size
- CSST Size (Low Pressure Gas only
¾ inch IPS
30/31 EHD
1 inch IPS
37 EHD
1½ inch IPS
60/62 EHD
Block and Bleed Valves (when used)
- Steel Pipe Size
- CSST Size (Low Pressure Gas only
Full IPS Relief
Increase IPS/CSST
one Size
Increase IPS/CSST
two Sizes
(12) Operating Sequencing. (See also 248 CMR 7.04, Initial Start-Up and Final Adjustments).
Each installation shall be equipped to provide for sequencing in accordance with the following
and in the order listed.
(a) Natural and mechanical draft systems with continuously burning pilot(s) capable of
igniting any gas flowing from the main burner shall, upon demand for heat:
1. Prove all interlocks.
2. Prove combustion air flow for mechanical draft systems.
3.
Prove in light-off position, if either an automatically operated damper, or an
automatically operated air shutter, or both, are employed.
4. Prove combustion (input) control, if employed, in light-off position.
5. Prove pilot(s).
6. Admit fuel to main burner.
7. Prove main flame, if required, in accordance with 248 CMR 7.03(4)(e).
8. Release combustion (input) control.
9. Upon flame failure at point of supervision, shut off fuel by primary safety control.
10. Shut off fuel to main burner on release from demand.
(b) Natural draft systems with intermittent pilot or interrupted pilot shall, upon demand for
heat:
1. Prove all interlocks.
2. Prove open for at least 90 seconds if either an automatically operated damper, an
automatically operated air shutter, or both, are employed.
3.
Prove in the light-off position if either an automatically operated damper, and
automatically operated air shutter, or both are employed.
4. Prove combustion (input) control, if employed, in light-off position.
5. Prove pilot(s).
6. Admit fuel to main burner.
7. Prove main flame, if required, in accordance with 248 CMR 7.03(4)(e).
8. Release combustion (input) control.
9. Upon flame failure at point of supervision, shut off fuel by primary safety control.
10. Shut off fuel on release from demand.
11. If an automatically operated damper is employed, return to stand-by position.
(c) Mechanical draft systems with intermittent pilot or interrupted pilot shall, on demand:
1. Prove all interlocks.
2. If an automatically operated damper is employed, prove in open position.
3.
Start fan(s) and prove air flow. Provide at least a four-air change purge of the
combustion chamber and equipment passes. The four air changes must be accomplished
in not more than 90 seconds with burners having maximum firing rate per combustion
chamber of not more than 2,500,000 Btu per hour. With burners having maximum firing
rates per combustion chamber in excess of 2,500,000 Btu per hour, the four air changes
shall be accomplished without time limitation by an air flow rate not less than 60% of the
air flow provided for the maximum firing rate.
4. Prove combustion (input) control and automatically operated damper, if employed,
in light-off position.
5. Prove pilot(s).
6. Admit fuel to main burner.
7. Prove main flame, if required, in accordance with 248 CMR 7.03(4)(e).
8. Release combustion (input) control.
9. Upon flame failure at point of supervision, shut off fuel by primary safety control.
10. Shut off fuel on release from demand.
11. If an automatically operated damper is employed, return to stand-by position.